We expressly point out that the VT51 ready-to-use heat transfer fluid or a heat transfer
fluid tested by us must be used in order to ensure long-term safe operation.
5. Expansion tank - dimensioning
-
for the correct dimensioning of the expansion vessel we recommend our easy system
planner (akotec.eu/english/easy-system-planner).
6. Storage
-
should be dimensioned between 50 l/m² and 70 l/m² gross collector area.
7. Controller
-
if no AKOTEC controller is used: the alternatively selected solar controller must have
a vacuum tube collector function
8. Insulation
-
complete and suff icient insulation of the solar lines is mandatory
9. Lightning strike
The collector array must be grounded against lightning in accordance with applicable
grounded in accordance with applicable regulations.
10. Air pot
The air pot must always be mounted at the highest point as well as at the flow.
Maintenance instructions
The antif reeze content of the heat transfer fluid & the
safety devices (safety valve and MAG) must be checked annually! A regular function
check of the control and the electrical components is required!
Note for the Weiser Protect 800, 1600 and 2400
The Weiser Protect without reflector also has absorbing vacuum tubes on the back.
The yield of the collectors can be increased by a reflective background on site, e.g. a
light-colored wall or reflective roof ing. reflective roof ing, the yield of the collectors can
be increased.