Doepke Dupline DNP 8A Manuale di istruzioni per l'uso - Pagina 6

Sfoglia online o scarica il pdf Manuale di istruzioni per l'uso per Sistemi I/O Doepke Dupline DNP 8A. Doepke Dupline DNP 8A 8. Output board

Doepke

11. Putting into Service

The circuit boards have to be operated with 24 VDC at terminals POW (24 VDC) and
BUS- (0 V). In order to avoid differences in potential, the common (O V) wire of the
voltage supply must be directly connected together with the Dupline signal con-
ductor (Dupline-) to the „BUS-" terminal. At no other point is a connection between
the two leads permissible. The internal 24 VDC voltage at the terminal DC+ of the
DNP 8A can be used as supply voltage for the loads at terminals O1..O8.
The Dupline signal must be routed to terminals DUP (Dupline+) and BUS- (Dupline-). At
no point within the system may the Dupline signal have a connection to earth potential.
The following table illustrates the connection configuration:
Terminal
O1
Output 1
O2
Output 2
O3
Output 3
O4
Output 4
BUS+
Dupline signal conductor +
(Dupline+)
POW
24 VDC operating voltage

12. Indicators

Indicator
Yellow LED
Dupline bus: Off: bus fault / On: bus OK
Green LED
Operating voltage: Off: no supply / On: operating voltage OK

13. Guarantee

All professionally installed, unaltered devices are covered by warranty during the statu-
tory guarantee period from the day of purchase by the end user. The guarantee is not ap-
plicable to damage incurred during transport or caused by short-circuit or overloading. In
the event of defects in workmanship or material, which are discovered within the guar-
antee period, the company will provide a replacement free of charge.

14. Technical Data

Dupline
Current input
Input / output channels None / 8
Outputs (DNP 8A)
Voltage drop
Breaking capacity
3931174/2009.06/E - The right to make technical changes reserved!
6
Description
Min.
Type NPN-transistors, not short-circuit-proof
Terminal
O5
Output 5
O6
Output 6
O7
Output 7
O8
Output 8
BUS-
Dupline signal conductor -
(Dupline-) and 0 VDC operating
voltage
DC+
Voltage for output load
Description
Typ.
100 µA
Description
Max.
1.2 V
200 mA