Cylon CBX-8R8 Scheda tecnica e manuale di installazione - Pagina 6
Sfoglia online o scarica il pdf Scheda tecnica e manuale di installazione per Controllore Cylon CBX-8R8. Cylon CBX-8R8 15.
Location
Illustration
DS0119 rev 40
©2018 Cylon
Service Port (Micro USB)
8-Way MS/TP address DIP switch (CBX only)
The controller's BACnet® MAC address can be set either electronically (USB or BACnet®) or manually using the 8-way
DIP
switch.
1)
Manual setting for ease of replacement: Setting the 8-way
then cycling the power, will force the controller to update its MAC address to match the
replace a manually-addressed controller in the field simply copy the
replacing.
2)
Electronic setting for remote configuration: Setting the 8-way
to be set electronically either locally by
It is also possible to use manual setting for initial commissioning, and then cycling the power to force the
controller to update its MAC address to match the
DIP switch
set the
to all zeros. The controller will retain the manually-set address until it is electronically
overwritten.
5-Way FLX bus address DIP switch (FLX only).
This sets the address of the FLX unit on its local FLX bus.
Output Override
(-H
variants only: CBX-8R8-H,
Bottom position: Off - outputs forced off.
Centre position: Auto - outputs are controlled by strategy.
Top position: Manual – for digital outputs, the output is forced on. For analog outputs the knob setting controls the
output value.
Note: Manual position is supervised, i.e. the strategy is aware of the manual value.
Inter-module connection sockets
Inter-module connector
FLX bus terminator
Indicator LEDs
Off
Red LED
Power is off
(Power)
Green LED
Unit is not
running
(Status)
Yellow LED
FLX bus
comms are ok
(FLX)
During firmware upgrade the Yellow LED will remain on while the strategy/comms section reboots, and then the
LEDs will rotate Red-Green-Yellow while the IO section reboots.
Note: During typical operation, the Red LED should be on, the Green
LED should be blinking, and the Yellow LED should be off.
All Rights Reserved.
Subject to change without notice
Description
DIP switch
to an address between 1 and 254, and
DIP switch
DIP switch
to all zeros will allow the MAC address
USB
or remotely over BACnet®.
DIP
settings. To enable subsequent electronic configuration,
FLX-8R8-H,
FLX-4R4-H)
On
Slow Blink
____ Unit Rebooting ____
Power is on
Strategy Loaded
Strategy Loaded and
but no network
device communicating
connectivity
on network
No FLX bus comms
FLX bus address clash
WWW.CYLON.COM
WWW.CYLON-AUTOMATRIX.COM
DIP
settings. To
setting of the controller you are
Fast blink
No Strategy
loaded
FLX bus comms
error
page 6 of 14