DOLD VARIMETER IMD RN 5897/321 Traduzione delle istruzioni originali - Pagina 2
Sfoglia online o scarica il pdf Traduzione delle istruzioni originali per Monitor DOLD VARIMETER IMD RN 5897/321. DOLD VARIMETER IMD RN 5897/321 17. Insulation monitor
Function
The device is supplied with DC auxiliary voltage via terminals A1(+) / A2.
Switching on the auxiliary voltage (Power-On) is followed by an internal
self-test for 12 s (see „Device test functions"). The test process is visible
with the status LED. After this, measurement of the insulation resistance
in the measuring circuits begins and the status LED changes into green.
Measuring circuit
(Insulation measurement between terminals L(+)/L(-) and PE)
The insulation monitor RN 5897/321 can only be used with a coupling
device. Max. mains voltage and connection diagrams have to be observed!
To connect the insulation Monitor RN5897/320 to a coupling device the
terminals with identical designations are connected (VSG1/L(+) and VSG2,
L(-)). The votage system to be monitored is connected to L(+) and L(-) of
the coupling device.
The type of the voltage system or the connection method (AC, DC, 3NAC)
has to be correctly adjusted via Modbus.
Also the terminals PE1 and PE2 have to be connected with 2 separate
wires to the protective earth. An interruption of a wire also causes a fault
signal (see section "Behavior on faulty connection"). The monitoring of
the PE connection cannot be de-activated.
To measure the insulation resistance an active measuring voltage with
changing polarity is connected between L(+)/L(-) and PE1/PE2.
At the end of a measuring cycle the actual insulation resistance is produced
and indicated. The relays for alarm K1 and pre-alarm K2 switch when
dropping under the adjusted response values. In addition the status LED
changes to orange color on pre-alarm or to red color on alarm.
The current measured value is output via Modbus. An asymetric insulation
resistance against „+" or „-" is also output via Modbus (only with DC networks
resp. insulation faults on the DC side).
Manual reset of fault message
The manual reset of insulation fault messages can be set via Modbus (alarm
memory). If the manual reset is activated, the insulation fault signals of the
measuring circuit remain saved when the adjusted response value is not
reached, even if the insulation resistance later goes back to healthy state
again. The minimum value of the insulation resistance is stored and can
be read out via Modbus. Pressing the „Reset" button on the front side for
2 s, the alarm signal and the stored minimum value are reset if the actual
insulation resistance is in healthy state.
The device can also be reset with a Modbus command.
Indicator relay for insulation fault signal
For the indicator relays K1 (contacts 11-12-14, for alarm) and K2 (contacts
21-22-24, for pre-alarm) the function can be set via Modbus to energized
on trip or de-energized on trip. When energised on trip the relays energize
when the value drops below the setting, when de-energised on trip, the
relays de-energize when the value drops below the setting. The status of
the indicator relays is also shown via Modbus.
Disable the measuring function
Using the external control input X1/X2 or via Modbus command the
measuring function of the RN 5897/321 can be disabled. This could be
used when several isolated voltage systems with individual insulation
monitors need to be coupled.
The measuring voltage is set to -90V (negative measuring phase) and
the evaluation of the measurement is stopped. The output relays switch
according to the current measured values. If the measurement is disabled
the status LED flashes continuously orange. Please be aware, only the
evaluation of the measurement is stopped and the measuring pulse is
interrupted! A high resistive disconnection to PE does not take place
(see internal resistance).
Function
Broken wire detection
As described in section "Measuring circut", the measuring circuits L(+) /
L(-) and the protective conductors PE1/PE2 are constantly monitored for
wire breaks – not only at Power-On or a manual or occasional automatic
test. The response time of PE1/PE2 monitoring is only a few seconds. The
response time of monitoring of L(+)/L(-) can be up to approx. 2 min. Broken
wire detection between L(+)/L(-) is performed via coupled alternating
voltage. This alternating voltage is short-circuited if the terminals are
connected to the connected mains at low-resistance. The device detects
that the mains to be monitored is properly connected.
Since this broken wire detection is carried out with alternating voltage, large
capacitances should be avoided between L(+)/L(-), since the capacitive
reactance of these capacitances also short-circuits this alternating voltage.
The device would no longer detect a connection fault on L(+)/L(-).
Especially parallel lines should be prevented over larger distances.
If larger capacitances between L(+)/L(-) cannot be avoided or if the coupled
alternating voltage interferes with the system, the broken wire detection can
be de-activated via Modbus. Monitoring deactivated, monitoring only during
device test or continuous monitoring (every 2 minutes for 10 s) are the
possible options. If the broken wire detection on L(+)/L(-) is de-activated
no AC voltage is injected. The broken wire detection on PE1/PE2 cannot
be de-activated.
Device test functions
Principally, 2 different test functions are implemented: The "self-test" and
the "expanded test":
The self-test of the device is performed automatically after Power-On and
every full operating hours. It can also be triggered manually at any time by
pressing the "Test" button at the device front for 2 s or via Modbus command.
With the self-test, contrary to the expanded test, the status of the Indicator
relays is not affected; the sequence is as follows:
The self test is indicated by the status LED with flash code 1 in orange colour.
Additionally, it is output via Modbus that the device is in test mode. First
the negative measuring pules is activated for about 5 s and the internal
measuring circuit is checked on failures. Then the positive measuring
pulse is activated for about 5 s and more internal tests are performed. If no
failures are detected, the normal measurement continuous. The extended
test is started, when during or at the end of above procedure (12 s) the
button "Test" is pressed again for 2 s or triggered via a Modbus command.
The procedure is the same as above (2 measuring phases with 5 sec each)
but in addition the output relays K1 and K2 go into alarm state. The Status
LED shows flash code 2 in orange colour and via Modbus it is signalled that
the device is in extended test mode. The test phases will be continuously
repeated. The extended test can be finished after the first complete
sequence (approx. 10 sec) by pressing the "reset" button for 2 seconds.
The device starts the insulation monitoring again. The extended test can
also be ended via a Modbus command.
U
Self test (Test 1)
Insulation
measurement
Duration: approx. 12s
measurement
Positive
Measuring voltage
Negative
1)
Test signal
2)
Reset signal
Alarm
Relay state K1 and K2
No Alarm
Test signal: Button Test > 2 s or X1/X2 > 1.5 s and < 10 s or
1)
via Modbus command
Reset signal: Button Reset > 2 s or X1/X2 < 1.5 s or
2)
via Modbus command
To initiate the extended test (Test 2) the test signal must be operated
3)
within the self test (Test 1) again.
The reset signal has here no function, as the first complete sequence
4)
of extended test (Test 2) is not finished.
2
Self test (Test 1)
Continuous extended
Insulation
Duration: approx. 12s
test (Test 2)
Duration: approx. 10s
3)
4)
12.07.22 en / 604A
Insulation
measurement
t
M12462