Cypress OSM-1000-BRD Manuale di avvio rapido
Sfoglia online o scarica il pdf Manuale di avvio rapido per Convertitore multimediale Cypress OSM-1000-BRD. Cypress OSM-1000-BRD 2. Osdp-wiegand converter
Anche per Cypress OSM-1000-BRD: Manuale di avvio rapido (2 pagine), Manuale di avvio rapido (2 pagine)
OSM-1000-BRD Quick Start Guide
OSDP-Wiegand Converter
What is included:
☐
OSM-1000-BRD (board only)
Product Overview:
The OSM-1000-BRD (board only) OSDP-Wiegand Converter is a general purpose Wiegand / OSDP
converter. The OSM unit has two operating modes, PD (Peripheral Device) mode and ACU (Access Control
Unit) mode. In PD mode, the OSM unit connects a traditional Wiegand reader to an OSDP ACU. In ACU
mode, the OSM unit connects an OSDP reader to a traditional Wiegand Access Controller. Additionally, two
OSM-1000 units can be used together, one in ACU mode and the other in PD mode, to connect a Wiegand
reader to a Wiegand Access Controller with an OSDP connection in between. The OSM-1000 meets OSDP
Verified conformance testing.
Pin Designations:
8 - 16 VDC Input
Ground
Data 0
Data 1
LED
Ground
Input 1
Input 0
DIP Switch Settings:
ON C & K
Set OSDP Polling
Address (0-15)
Invert
Enable
Secure
Channel
Beep on
Read
(ACU Mode)
OSDP Default Parameters:
Secure Channel Base Key (SCBK): 303132333435363738393A3B3C3D3E3F
Polling Address: 0
Baud Rate: 9600
For more detailed information on the OSM-1000 visit CypressIntegration.com.
☐
Warranty
DIP Switches 1-4: Set the OSDP Polling
ON
Address in PD mode. Set the OSDP Address
to be polled by the OSM unit in ACU mode.
See the DIP Switch Address Table to the right.
DIP Switch 5: When ON, enables the Beep on
OFF
Read feature when in ACU mode.
DIP Switch 6: When ON, OSM-1000 will only
Mode
Select
establish Secure Channel communication
sessions.
LED
DIP Switch 7: When ON, inverts osdp_LED
command sent to PD when in ACU mode; and
inverts the state of the output pin based on
osdp_LED command received in PD mode.
DIP Switch 8: When ON, the OSM-1000 is set
to ACU mode. When OFF, the OSM-1000 is
set to PD mode.
☐
Quick Start Guide
RS-485 -
RS-485 +
Ground
Strike N.O.
Strike COM
Strike N.C.
Ground
8 - 16 VDC Input
DIP Switch Address Table
1 2 3 4
Address #
Address 0
X
Address 1
X
Address 2
X
X
Address 3
X
Address 4
X
X
Address 5
X
X
Address 6
X
X
X
Address 7
X
Address 8
X
X
Address 9
X
X
Address 10
X
X
X
Address 11
X
X
Address 12
X
X
X
Address 13
X
X
X
Address 14
X
X
X
X
Address 15
X = ON
201223