Blueridge BA14 Manuale di istruzioni per l'installazione - Pagina 8
Sfoglia online o scarica il pdf Manuale di istruzioni per l'installazione per Condizionatore d'aria Blueridge BA14. Blueridge BA14 19. (single-stage) air conditioner
4
WRAP SERVICE VALVES
To help protect service valve seals during brazing, wrap water-saturated cloths around service valve bodies and copper tube stubs. Use
additional water-saturated cloths underneath the valve body to protect the base paint.
5
FLOW NITROGEN
Flow regulated nitrogen (at 1 to 2 psig) through the refrigeration gauge set into the valve stem port connection on the liquid service valve and
out of the vapor valve stem port. See steps 3A, 3B and 3C on manifold gauge set connections.
6
BRAZE LINE SET
Wrap both service valves with water-saturated cloths as illustrated here and as mentioned in step 4, before brazing to line set.
Cloths must remain water-saturated throughout the brazing and cool-down process.
IMPORTANT —
additional water-saturated cloths to help cool brazed
joint. Do not remove water-saturated cloths until
piping has cooled. Temperatures above 250ºF will
damage valve seals.
FIRE, PERSONAL INJURY, OR PROPERTY DAMAGE
may result if you do not wrap a water-saturated cloth around
both liquid and suction line service valve bodies and copper
tube stub while brazing the line set! The braze, when
complete, must be quenched with water to absorb any
residual heat.
Do not open service valves until refrigerant lines and
indoor coil have been leak-tested and evacuated. Refer
to Leak Test and Evacuation section of this manual.
7
PREPARATION FOR NEXT STEP
After all connections have been brazed, disconnect manifold gauge set from service ports. Apply additional water-saturated clot h s to both
services valves to cool piping. Once piping is cool, remove all water-saturated cloths.
Page 8 of 19
WHEN BRAZING LINE SET TO
SERVICE VALVES, POINT FLAME
AWAY FROM SERVICE VALVE.
Allow braze joint to cool. Apply
WARNING
VAPOR LINE
LIQUID LINE SERVICE VALVE
VAPOR LINE
SERVICE VALVE
Issue 2212
WARNING
While protecting the
service valve seals with
water-saturated cloths,
ensure that water does
NOT enter the system.
WATER-SATURATED
CLOTH
LIQUID LINE
WHEN BRAZING LINE SET TO
SERVICE VALVES, POINT FLAME
AWAY FROM SERVICE VALVE.
WATER-SATURATED
CLOTH
508255-01