Ambi-Rad OFSU100 Istruzioni per l'installazione, la messa in servizio e la manutenzione - Pagina 14

Sfoglia online o scarica il pdf Istruzioni per l'installazione, la messa in servizio e la manutenzione per Riscaldatore Ambi-Rad OFSU100. Ambi-Rad OFSU100 15. Oil fired unit heaters

4 Components drawing
Components list
1. Exchanger
2. Safety thermostat STB
3. Burner thermostat TW
4. Fan thermostat TR
5. Burner plate gasket
6. Flame glass
7. Burner plate
8. Air distribution louvres
9. Terminal board
10. 7 poles connector
11. Fan
12. Fan

5 Technical data

Fan features table
Model
No on drwg
OFSU32
11
OFSU40
12
OFSU70
11
OFSU100
11
OFSU100
12
Burner set up table
Model
Air setting
OFSU32
5.0
OFSU40
5.4
OFSU70
5.0
OFSU100
5.0
Setting of thermostats
Type
TR Thermostat
TG Thermostat
STB Thermostat
12
OFSU32
G10130
G09070
G02750
G02781
G01190
G02317
G10115
G10030
G10025
B02455
Code
Fan No
G00908
G11020
G00908
G00908
G11020
Pump pressure
13.8bar
13.2bar
12.0bar
12.0bar
OFSU32
30-35˚C
70-75˚C
100˚C
OFSU40
G10130
G09070
G02750
G02781
G01190
G02317
G10115
G10030
G10025
B02455
Technical data table section 5
Technical data table section 5
Motor Power
1
150
1
245
2
150
2
150
1
245
CO
%
Smoke
2
11.8
11.7
12.5
11.5
OFSU40
30-35˚C
75-80˚C
100˚C
OFSU70
G10140
G09070
G02750
G02781
G01190
G02317
G10115
G10030
G10025
B02455
Fan Dia (mm)
Blades No
450
4
450
4
450
4
450
4
450
4
Flue gas (approx)
0
193˚C
0
241˚C
0
220˚C
0
197˚C
OFSU70
30-35˚C
70-75˚C
100˚C
OFSU100
G10150
G09070
G02750
G02781
GF01190
G02317
G10115
G10030
G10025
B02455
Blades Angle
23˚
27˚
23˚
23˚
27˚
Nozzle Size
0.65 x 60˚s
0.85 x 60˚s
1.35 x 60˚s
2.00 x 45˚s
OFSU100
30-35˚C
75-80˚C
100˚C