4 INSTALLATION AND OPERATION
The following sections provide guidelines for installation; location and mounting, wiring, and
cable selection.
4.1 LOCATION AND MOUNTING
Mount the AMC-SIR Refrigerant Gas sensor/transmitter on a solid, non-vibrating surface or
structure in an area where the ambient concentration of gas is not directly affected by the
presence of clean air supply, ventilation systems, or blockage by surrounding articles and
sources of interference gas or contaminants. The AMC-SIR Refrigerant Gas sensor/transmitter
shall be installed in an area where refrigerant from a leak is most likely to concentrate. The
installer is required to provide the necessary mounting hardware for the unit. There is a 7/8"
conduit hole for the installation wiring located on the bottom of the enclosure, refer to Fig. 4-1.
Warning:
Mount enclosure with the sensor located as shown in Figure 4-1. This will ensure
correct orientation.
4.1.1 WALL MOUNTING
Warning:
Choose appropriate conduit hardware as to not interfere with internal components.
Figure 4-1 Enclosure Mounting