7. Configuration of AVM 1002DX

The front panel of the AVM 1002DX module contains three buttons, labelled subsequently
UP, DN and SET. These buttons are used to edit the module functions.
7.1

Entering the menu

During normal operation of the AVM 1002DX module, pressing UP or DN button will cause
entering into the device menu, which is indicated by rapid blinking of the OK LED. While in
edit mode, buttons UP/DN scroll the menu items:
A – alarm,
U – warning,
d – thresholds activation delay,
L –
latching
of alarm threshold or warning threshold
CA – alarm activation in case of the sensor circuit failure,
CU – warning activation in case of the sensor circuit failure,
SC – correction of values indicated by the module,
Er – turning display off on sensor failure,
AU – selection of vibration signal estimate,
ATTENTION! In some types of AVM 1002DX modules some of the above functions are not
active.
7.2

Setting up of the alarm threshold 'A'

The AVM 1002DX has the ability to activate the built-in relay, when the signal from the vibration
sensor exceeds the threshold value.
To set the alarm threshold one should perform the following procedure:
1. Press UP/DN. Afterwards the OK LED will blink rapidly, which indicates entering into the
device menu.
2. By pressing UP/DN set the letter 'A' on the display.
3. Confirm by pressing the SET button.
4. Use the UP/DN buttons to select the desired alarm threshold value in the range from 0.0 to
99. Alarm threshold value cannot be lower than the warning threshold value.
5. To confirm the change, press the SET button.