- ページ 14
除湿機 Coaire CNCM10のPDF インストレーション&オペレーションマニュアルをオンラインで閲覧またはダウンロードできます。Coaire CNCM10 18 ページ。 Non-cycling refrigerate air dryers
PE
Legend:
IG : Rocker On/Off switch
K : Refrigeration compressor
KR : Compressor start-up relay
KM : Compressor electric motor
KT : Compressor thermal protection
Only qualified personnel should perform maintenance operations.
Prior to performing any maintenance or service, be sure that:
• Ensure that the power is off and the unit is at atmospheric pressure.
• Main power circuit breaker is in the off position per lock out/tag out procedures.
• Ensure that maintenance personnel have read and understand the safety and operations instructions in
this manual.
High temperature conditions exist during operation of system. Avoid contact until system or component
has dissipated heat.
DAILY
• Verify that the DewPoint displayed on the DMC11 is correct.
• Check the proper operation of the condensate drain system.
• Inspect the condenser for cleanliness.
EVERY 200 HOURS OR MONTHLY
• Blow entire unit out with compressed air (Max. 30 psig - 2 barg)
• Blow condenser coils out with compressed air.
• Close the manual condensate drain valve, remove the mechanical filter and clean it with compressed air
and a brush. Reinstall the filter, make sure it is tight, and open the manual valve.
• Verify operation of the machine.
EVERY 1000 HOURS OR YEARLY
• Tighten all electrical connections. Look for broken, cracked or bare wires.
• Inspect refrigeration circuit for signs of oil and refrigerant leakage.
• Measure and record amperage. Verify that readings are within acceptable parameters as listed in
specification table.
• Inspect condensate drain flexible hoses, and replace if necessary.
• Verify operation of the machine.
5.21 ELECTRICAL SCHEMATIC CNCM10 & CNCM18
Pui
PO
ssa
WE
nce
R
N
COM
B
EVB
6.1 MAINTENANCE SCHEDULE
DMC5
Air Dryer Controller
PROBE
Sonde
D
Vc
PR
M
EVD
VC : Condenser fan motor
PR : DMC5 probe
EVB : Hot gas by-pass solenoid valve
EVD : Condensate drain solenoid valve
13
M