MOV and INC, in order to store the data.
 The installation height and the full distance value are parameters must
be set up by users, and others are optional ones.
 Press SEL and MOV simultaneously to exit the operating status and store
the settings.
Significance of the alphabet and the corresponding operating mode:
The operating mode
Installation height
Level full scale
The inner password

5. Calibration

The level meter should be calibrate indoor before installation to ensure the
normal performance.

General consideration

 Let the probe be perpendicular to a wall, and make sure the measuring
distance is larger than the blacking distance, and no barriers within the
beam angle zone.
 Wiring and connecting the instrument correctly according to the
guideline.
 Turn on the power and after a few seconds the instrument will enter the
running mode. And check the level value 、the empty value and the
temperature value in turn through SEL key.
 Move the probe slowly, the level value and the empty value should
change slowly accordingly.
 Press SEL and MOV keys simultaneously and then enter the operating
mode. Advise the installation height value, the displayed level value
and empty value should change accordingly.
 Advise the full distance value , and the output current should change,
too. Because the output current is always in accordance with the level
value.
 Advise the limit value, and test with a multi-meter whether the relays
act in correct time delay.
Significance
The distance from the surface of the probe to the
bottom of the container
The full range corresponding to the output 20mA
The password for inner parameter's operating. Users do
not need to set up this parameter.
14