Press "+"key in the input state to change the value or symbol of cursor circularly.
Press "<"key to move the current cursor one position towards the right.
Max.8 digits inputting is allowed.(including the symbol,decimal).
2.Menu Operation
In the menu browse:
Press "+" key for page down;
Press"<"key for page up;
Long Press"<"key for entering into the sub-menu;
Long press "+" key for returning to the working screen figure 2;
In the sub-menu,long press "+" key to quit out;long press "<"key to enter into
modified state;In the modified state,press "+" key for downward selecting;press
"<"for upward selecting;long press "<"key for confirmation and saving.
Attention:When the parameter setting,it should long press "<"key for saving the
displaying.Otherwise,the setting is invalid.
User Parameter Setting Menu
Sub-menu
Display of
Series#
menu
Flow Unit
1
select
Algorithm
2
Selection
Flow
3
Coefficient
Maximum
4
Output Flow
Density
5
setting
Temperature
6
Setting
Absolute
7
pressure
setting
Low flow cut
8
off
AKTEK Endüstriyel Ekipman ve Enstrümantasyon LTD.ŞTİ.
İMES Sanayi Sitesi B-Blok 204.Sok. No:40 Y.Dudullu-Ümraniye/İSTANBUL
Alternative options or range of value
Definition
0:m
3
/h
Flow Unit select
2:l/h
(default 0)
4:t/h
6:kg/h
00:Conventional Volume flow
Algorithm
01:Conventional mass flow
Selection
02:Volume flow of conventional gases
(default 0)
03:Mass flow of conventional gases
Flow Coefficient
Set the meter coefficient with the unit of P/m3
(default 3600)
When the meter outputs 4~20mA analog signal, must set the value and
Max. Flow
the value cannot be zero,the unit should be accordance with the flow
(default 1000)
unit.
Density setting
When Algorithm Selection is setting to mass flow(01,03),it must set
(default 1.0)
this item,the unit is kg/m3
Temperature
Setting the temperature calculated value,when choose 02,03,04,06
Setting
algorithm,it must set this item,the unit is Celsius degree.
(default 0.0)
Gas Absolute
Setting the absolute pressure of gas,when choose 02,03 algorithm,it
pressure set
must set this item,the unit is Kpa.(when vacuum is 0.0,it will cause the
(default
flow is 0)
101.325)
Set percentage
The value is between 0~100
of resection
14
1:m
3
/m
3:l/m
5:t/m
7:kg/m