5) RELAY OUTPUTS:
a. Type:
b. Contact Rating:
c. Hysteresis:
d. Setpoints:
e. Stability:
6) ALARM INDICATION:
a. Open Pickup Alarm:
b. Trip Indication:
7) MEMORY:
8) CONNECTORS:
9) MECHANICAL:
10) ENVIRONMENTAL:
a. Operating Temperature Range:
b. Storage temperature:
c. Vibration:
11) AGENCY APPROVAL:
12) PROGRAMMING
a. PC / Windows based:
SPDT relay contacts (isolated dry contacts)
6.0 Amps @ 28 VDC or 115 VAC
1/8 HP @ 120 / 240 VAC (100,000 cycles)
1.5 / 0.8 Amps @ 120 / 240 VAC, Pilot Duty (100,000
cycles)
3.8 / 1.9 Amps @ 120 / 240 VAC general Use (100,000
cycles)
Selectable (1% of full-scale frequency default)
Programmable for:
i. Overspeed / under speed trip
ii. Energize or de-energize when setpoint reached
iii. Latching or non-latching (auto reset)
iv. Underspeed setpoints are Class C Logic (active
once normal)
v. Latched relays are reset via digital input
Less than 0.05% of setpoint change with a 10%
change in supply voltage. Temperature coefficient
±0.01% per °F (±0.018% per °C)
LED indication if open pickup sensed
Option to trip relay
LED indication if a relay tripped condition
All configuration parameters retained if power lost
Removable Phoenix type
DIN rail mount package
-40 to +70 DegC
-40 to +80 DegC
Per modified Mils STD 810-E
CSA Class I, Div. 2, Groups A, B, C, D
CE for Electromagnetic Compatibility:
Meets all EMC requirements of IEC 61326-1: 2012 &
Refer conformity certificate for more details.
*Not applicable for "-I" configurations.
Meets all RoHS requirements.
Windows XP, Vista & Windows 7 & 8 compatible
USB port for programming, uploading & downloading