- ページ 6

煙警報器 EKHO EK-WL8-OV/AUのPDF クイック・スタート・マニュアルをオンラインで閲覧またはダウンロードできます。EKHO EK-WL8-OV/AU 9 ページ。 Wireless optical smoke detector with build-in voice annunciator and visual alarm device

STFV.425238.037-AU-UM rev. 23
SOUNDER
The EK-WL8-OV/AU sounder may generate three messages.
For normal operation it is necessary that the message number set in the translator
and in the device match.
Mess. Pattern
Pulse signal 2500 Hz (pattern ISO 8201 Evacuate signal)
1
2
Voice message 2 (Fire! Fire! Please leave the building by the nearest exit)
3
Voice message 3 (Fire! Fire! Please leave the building by the central exit)
Voice sounders sequence and timing:
Sequence step
a) attention-drawing signal
b) silence
c) voice message (for message 2 and 3)
d) silence
NOTE All voice messages may be rerecorded by using "OrpheyRLib" special utility
from "Streletz-Wizard" software and special tool (Programmer-PRO device, see
STFV.425238.037-D5 EK-WL8-OV).
Total duration of all messages up to 20 sec
EK-WL8-OV/AU
WIRELESS OPTICAL SMOKE
DETECTOR
WITH BUILD-IN VOICE ANNUNCIATOR
AND VISUAL ALARM DEVICE
20.08.2020
Phase a: = Sine for 0.5±0.05s
Phase b: = Silence for 0.5±0.05s
Phase c: = Silence for 1.5±0.15s
Total cycle to last 4.0±0.4s
Page 6 from 9
Duration
2,5 s
0,75 s
3,9 s
0,85 s
6