- ページ 2
コントローラー Ekinex EK-E12-TP-BG-NFWのPDF データシートをオンラインで閲覧またはダウンロードできます。Ekinex EK-E12-TP-BG-NFW 5 ページ。 Pushbutton
Ekinex EK-E12-TP-BG-NFW にも: クイック・スタート・マニュアル (9 ページ)
Completion of the pushbutton
The pushbutton is completed through a separate order of:
• a set of rockers that allows the use as a 1-fold, 2-fold
or 4-fold pushbutton;
• a 1-fold plate (square, EK-PQS-...) or a 2-fold plate
(rectangular, EK-P2G-... or EK-P2S-...) in combination
with another bus device of 71 Serie or a 55 x 55 mm
fl ush-mounting insert;
• a square frame of the ekinex
for the 'NF - No Frame versions).
Rockers
Three-positions rockers with central neutral position have
to be mounted on the pushbutton. Pushing one side of
a rocker (for example the upper one), the pushbutton
sends on the bus a telegram for switching on, increasing
the brightness of luminaires or raising the blinds, while
pushing the other side (for example the lower one), it sen-
ds a telegram for switching off , reducing the brightness of
luminaires or lowering the blinds. Each channel is equip-
ped with LEDs which can be freely programmed as status
feedbacks of the loads and as orientation nightlight.
Code set of
Appea-
Nr. and type of
rockers *
rance
EK-T1Q-xxx
EK-T2R-xxx
EK-T4Q-xxx
EK-T4R-xxx
(*) To be completed with the extension for the colour: xxx = MAA (white), xxx = GAG
(silver), xxx = MAL (black)
Plate
The pushbutton may be completed by a square 1-fold pla-
te or by a rectangular 2-fold plate. In both cases the plate
must be necessarily provided with a 60 x 60 mm window
for the mounting of the device.
Plate
Type
Appearance
code *
EK-PQS-...
1-fold **
EK-P2G-...
2-fold ***
EK-P2S-...
2-fold ***
(*) To be completed with the extension for colour, material and fi nishing
(**) For mounting without frame ('NF) it requires the EK-TAQ adapter
(***) For mounting without frame ('NF) it requires the EK-A71-... adapter
Frame
The pushbutton can be completed by a square 1-fold fra-
me or by a rectangular 2-fold frame of the fl ank or form
series. The 'NF (No Frame) versions of the pushbutton do
not require any frame.
form or fl ank series (not
®
Modularity
rockers
[mm]
1 square
60 x 60
2 rectangular
30 x 60
4 square
30 x 30
4 rectangular
60 x 15
Window modula-
rity [mm]
60 x 60
55 x 55 (1)
60 x 60 (1)
60 x 60 (2)
Mounting
The device has degree of protection IP20, and is there-
fore suitable for use in dry interior rooms. The installation
of the device diff ers depending on the mounting with or
without frame ('NF series).
Mounting with frame
Carry out the following steps:
• fi x the metallic support (h) with the pair of screws (g) on
the fl ush-mounting box (i) equipped with fi xing holes at
60 mm distance;
• press for fi xing the pushbutton (d) on the adapter (e);
• insert pushbutton and adapter (d+e) in the metallic sup-
port (h). Mounting the device follow also the indication
TOP (arrow tip pointing up) on the rear side of the de-
vice;
• snap a square frame (f) of the form or fl ank series, in-
serting it from the rear of the pushbutton (d);
• enter the bus terminal block, previously connected to
the bus cable in its slot on the rear side (see also: "Con-
nection of the KNX bus line"). At this point it is recom-
mended to carry out the commissioning of the device
(see also "Confi guration and commissioning") or at le-
ast the download of the physical address;
• fasten the device on the metallic support supplied with
the pair of screws (c);
• snap the rockers (b) for the operation of the device;
• snap the plate (a).
a
b
c
Mounting with frame
a) 1-fold plate
b) Rockers
c) Fixing screws (for device)
d) Device (pushbutton 71 Serie)
e) Adapter for mounting with frame (included in the delivery)
f) Frame (square, form or fl ank series)
g) Fixing screws (for metallic support)
h) Metallic mounting support
i) Flush-mounting box
Mounting without frame ('NF series)
Carry out the following steps:
• insert the metallic support (f) on the adapter (g);
• fi x adapter and support (f+g) with the pair of screws
(e) on the fl ush-mounting box (h) equipped with fi xing
holes at 60 mm distance;
• enter the bus terminal block, previously connected to
the bus cable in its slot on the rear side (see also: "Con-
nection of the KNX bus line"). At this point it is recom-
mended to carry out the commissioning of the device
(see also "Confi guration and commissioning") or at le-
ast the download of the physical address;
• insert the pushbutton (d) on the metallic support (f);
• fasten the device on the metallic support supplied with
the pair of screws (c);
• snap the rockers (b) for the operation of the device;
• snap the plate (a).
2
d
e
g
f
h
i