Product Specifications
- Power Source: 20-30VAC, Class II, 50/60Hz.
- System Mode: Heat, Cool, Auto, Emergency Heat and
Off
- Fan Mode: Auto and On
- Cooling setpoint temperature range: 65F - 90F,
18.0C - 33.0C, 1F and 0.5C resolution.
- Heating setpoint temperature range: 40F- 85F,
5.0C - 30.0C, 1F and 0.5C resolution.
- Default set points: 68F, 20.0C Heat, 78F, 25.5C Cool
- Storage Range: -40F to 140F, 5% - 90% RH non-con-
densing.
- Operating Temperature range: 32F - 110F, 5 - 90% RH
non-condensing.
- Outdoor Temperature Display Range: -40F - 140F.
- Minimum Cycle Off Time Delay: Cooling - 5 minutes,
Heating - 1 minute.
- Use minimum 18 gauge NEC approved control wiring.
▲
CAUTION
!
To prevent shortening its service life, the control should not
be installed until construction is completed.
Installation
Comfort Control - Location
The Comfort Control should be mounted approximately 60"
(1.5m) off the floor on an interior partition wall. Never install
the Comfort Control on an outside wall.
For proper temperature sensing, avoid mounting the
Comfort Control where it will be exposed to heat radiated
from lamps, sun light, fireplaces or any other radiant heat
sources.
Avoid locations close to windows, behind doors or alcoves with
poor air circulation, adjoining outside walls, or doors that lead
to the outside.
Select a location that prevents the Comfort Control from
being directly exposed to air currents from supply registers.
Mount the Comfort Control on a section of interior wall that
does not contain hot and cold water pipes or ductwork.
Outdoor Sensor - BAYSEN01ATEMPA - Location
Careful consideration of the following recommendations will
help the outdoor sensor provide continuous accurate readings:
1. Mount the outdoor sensor on the north facing side of the
building in an area where it is exposed to freely circulat-
ing airflow and out of direct sunlight.
2. Do not allow hot air airflow from the attic or drafts from
inside exterior walls to bias the sensors operation.
Always seal the hole where control wiring passes to the
outside of the structure. Use non-hardening caulk, putty,
or insulation.
3. Avoid locations such as near dryer vents or placing the
sensor close to, or directly above the outdoor unit where it
would be exposed to hot discharge air from the condenser
fan.
4. Maximum length of field wiring cable to sensor is 200
feet.
5. Minimum wire gauge is 18AWG.
Mounting and Wiring
1.Turn OFF all power to heating and cooling equipment.
2. If an existing thermostat is being replaced:
a. Remove existing thermostat from wall.
2
properly. If the Comfort Control is replacing a thermostat
that contains mercury in a sealed tube, do not place your old
thermostat in the trash. Contact your local waste manage-
ment authority for instructions regarding recycling and the
proper disposal of an old thermostat.
3. Separate the control from the mounting base to expose
4. Slide the mounting base drawer out to expose all the
5. Drill two mounting holes in wall where marked.
6. Secure mounting base to wall with 2 screws (use anchors
7. Adjust length and routing of each wire to reach proper
© 2007 American Standard Inc. All Rights Reserved
Installer's Guide
OT1
RS1
OT2
RS2
Y
b. Disconnect wires from existing control, one at a time. Be
careful not to allow wires to fall back into the wall.
c. As each wire is disconnected, record wire color and
terminal marking.
d. Discard or recycle old thermostat.
Mercury is a hazardous waste and MUST be managed
mounting holes by pressing the release button A on the
bottom of the control with the thumb of one hand while
gripping the subbase by the mounting holes with the
other hand. Lift out and up. See Figure 1.
mounting holes. Route control wires through the large
hole in mounting base.
Level mounting base against wall (for aesthetic value
only) and mark wall through 2 mounting holes. See
Figure 2.
provided if needed). Additional mounting holes are
available for more secure mounting if needed.
Make sure all wires (including the 2 outdoor sensor wires)
extend through hole in mounting base.
terminal on the connector block on mounting base. Strip
only 1/4-in. of insulation from each wire to prevent
adjacent wires from shorting together when connected.
Figure 1
Fold Business
card & insert
into slot
Figure 2