調光器 Ekinex EK-GD1-TP-4-HVのPDF セットアップとインストールマニュアルをオンラインで閲覧またはダウンロードできます。Ekinex EK-GD1-TP-4-HV 6 ページ。 Vac 4-channel phase cut dimmers
Installation diagrams
The device can be installed by wiring the outputs either
with a separate COM pole or with a common COM pole.
Therefore the following schemes can be created:
1. Outputs with separate COM pole connection
Power
EK-GD1-TP-4-HV
Dimmer KNX 90-230V~ 50/60 Hz
Out: 4x 200W
1
2
3
4
Installation diagram with outputs connected
to the separate COM pole
2. Outputs with common COM pole connection
The terminals indicated by the COM label can be used as
a common terminal for the loads.
Power
EK-GD1-TP-4-HV
Dimmer KNX 90-230V~ 50/60 Hz
Out: 4x 200W
1
2
3
Installation diagram with outputs connected
to the common COM pole
L
90-230 Vac
50-60 Hz
N
-
KNX
+
bus
L
90-230 Vac
50-60 Hz
N
4
-
KNX
+
bus
!
Warning! The input N terminals must never be con-
nected to the COM outputs.
Warning! In configuration 2, the internal fuse on
!
the load, which implements overcurrent protection,
does not trip.
The electronic short circuit protection remains fun-
ctional.
Commissioning
For commissioning the device the following activities are
required:
• make the electrical connections as described above;
• turn on the bus power supply;
• switch the device operation to the programming mode
by pressing the programming pushbutton (5) loca-
ted on the front side of the housing. In this operating
mode, the programming LED is turned on;
• download into the device the physical address and the
configuration with the ETS
At the end of the download the operation of the device
automatically returns to normal mode; in this mode the
programming LED is turned off. Now the bus device is
programmed and ready for use.
i
Note. The configuration and commissioning of KNX
devices require specialized skills. To acquire these
skills, you should attend the workshops at KNX cer-
tified training centers.
Device reset
To reset the device, remove the power from the KNX bus;
then press the programming button and, keeping it pres-
sed, restore power to the KNX bus: if, after approximately
10 s, the programming LED flashes quickly, it means that
the reset has been carried out. At this point it is necessary
to re-address and configure the device via ETS.
!
Warning! The reset operation brings back the devi-
ce to its factory delivery state. The addressing and
value of the parameters set during configuration are
lost.
4
program.
®