Terminal blocks for connection of inputs and outputs
Nr.
Marking
Connection
1-2
L
AC - L input
3-4
N
AC - N input
5
OUT1
CH1 - L output
6
N
N - output
7
OUT2
CH2 - L output
8
N
N - output
9
OUT3
CH3 - L output
10
N
N - output
11
OUT4
CH4 - L output
12
N
N - output
Nr.
Marking
Connection
1-2
DALI IN
DALI input
4-5
DALI OUT
DALI output
Mounting
The device has degree of protection IP10, and is there-
fore suitable for use in dry interior rooms. The housing is
made for rail mounting according to EN 60715 in boards
or cabinets for electrical distribution. The correct mounting
is when the 230 Vac spring terminal is located at the bot-
tom. When installing be sure to leave accessible only the
front panel; all other sides must not be accessible. For the
mounting proceed as follows:
• with the aid of a tool bring the locking device in the fully
lowered position (a);
• place the upper edge of the rear inner profile on the
upper edge of the rail (b);
• rotate the device towards the rail (c);
• push the locking device upward until it stops (d).
a
c
Before removing the device, be sure that inputs, outputs,
and the 230 Vac power supply have been disconnected.
Use a screwdriver to slide down the locking device and
remove the device from the rail.
i
Note. When mounting the device in boards and ca-
binets it shall be provided the necessary ventilation
so that the temperature can be kept within the ope-
rating range of the device.
Connection of the DALI bus line
The connection to the DALI bus network is done via the
spring terminal, located on the front of the device in the
upper part.
Characteristics of the DALI terminal block
• Spring tightening of the conductors
• Bus wiring: 0.2 ÷ 1.5 mm
• Conductor stripping recommended approx. 10 mm
• Maximum length of the connection between dimmer-
driver and control device <10 m
• Length of connection cables <25 m
Connection of power supply and loads
The connection of the 230 Vac 50/60 Hz power supply is
made with the spring terminals 1-3 or 3-4 (L, N) located at
the bottom front of the device.
Characteristics of the supply and loads terminal block
• Spring tightening of the conductors
• Max section of conductors 2.5 mm² - 12 AWG
• Wire stripping recommended approx. 11.5 mm
2
b
d
- 30 ÷ 16 AWG
2