- ページ 3

コントローラー Dontek Aquasmart 5 RPのPDF 取扱説明書をオンラインで閲覧またはダウンロードできます。Dontek Aquasmart 5 RP 4 ページ。 Automatic solar controller

Dontek Aquasmart 5 RP 取扱説明書
REPORTED TRANSMITTER FAULTS
If the following messages are displayed, then action is to
be taken to rectify the fault(s)
"WAITING FOR ROOF TRANSMISSION"
The AQUASMART cannot receive a roof temperature from
the radio transmitter or more than 50 minutes have
elapsed since the last transmission, check installation as
per instructions.
.
OPERATING INSTRUCTIONS
LCD SCREEN
The LCD screen displays the pool and roof temperatures,
solar temperature limit, pump on status, on/off/locked-out
status and the time of day & date (clock).
LCD INDICATORS
There are arrow icons on the LCD screen that point to
current mode text on the label.
MODE BUTTON
Pressing this button changes to the next mode of
operation in the following order; Heating / Manual /
Standby.
Once the mode button is no longer being pushed then the
selected mode of operation is automatically saved.
Heating mode (Auto)
is the normal operating mode for
heating the pool.
Manual mode
is for testing the pump installation on a cold
or cloudy day. Once manual mode is selected the pump will
start. After manual mode time-outs, unit will return to the
previous mode.
Standby mode
of operation is for off-season maintenance
or if pool heating is not required. This is a better option
than turning off the controller as it will flush treated pool
water through the solar system as well as prolong pump
bearing and mechanical seal life. The pump will run for 3
minutes each day from when the Standby mode was
selected or at 10am if the time-clock mode was selected
.
**The factory default for SOLAR MODE is Heating
MODE
↑ AND ↓ BUTTONS (TEMPERATURE SETTING)
Adjusting the temperature limit will allow the controller to
heat the pool until the temperature limit +½°C is achieved,
heating will then remain off until the sample wait period
expires, if no sample wait period is active the heating will
remain off until the pool temperature drops ½°C below the
temperature limit setting, due to rounding the actually
heating hysteresis is ±½°C.
The ability to solar heat the pool will depend on weather
conditions.
** The factory default for SOL. LIMIT is 30°C
AQUASMART 5 RP v1.2
"ROOF SENSOR DISCONNECTED"
Check that the temperature sensor is firmly connected to
the terminals. Cable joints must also be soldered and
sealed (preferably with heat shrink). An unbroken but
damaged cable can also cause this fault
ENTER BUTTON
Pressing the ENTER button will turn on the LCD backlight,
pressing the ENTER button while the backlight is lit will
enter the SETTINGS MENU;
The following will be displayed;
1) EXIT
The menu system can be navigated using the ↑ or ↓
buttons, all selectable and changeable values will flash on
the LCD screen. Press the ENTER button to accept the
currently displayed (flashing) item.
All menu items are shown below;
1) EXIT
2) CLOCK
3) SYSTEM
1) EXIT
Press ENTER on this menu to return to automatic
operation.
2) CLOCK
When selecting the clock you will have to set the time of
day.
3)
SYSTEM
System sub-menu;
EXIT
LCD TIME
HOURS
EXIT - Press ENTER on this menu to return to automatic
operation.
LCD TIME – Adjust the number of seconds the backlight
remains on after the time a button was pressed. (Select
NONE for always on.)
HOURS – is for hours of solar operation (
selecting the start time in hour intervals
Then the end time
(12:00 – 21:00)
installer setup is run from 12:00-12:00 (24hrs).
24hr)
first
(6:00 – 12:00)
Factory default for
**
3