- ページ 13
バスタブ Astor-Bannerman KivaのPDF 取扱説明書と取付説明書をオンラインで閲覧またはダウンロードできます。Astor-Bannerman Kiva 17 ページ。 Height adjustable bath
Commissioning shower mixer
Maximum temperature setting:
Before using the shower, the maximum temperature must be checked to make sure that it is at a
safe level. It has been preset to approximately 43°c at the factory but due to variations in site
conditions, the maximum temperature may need adjustment. Note: Make sure that the hot water
temperature is at least 55°c and that there is sufficient supply. Note: For Type 3 valves in
healthcare installations the maximum blend temperature is determined by the application, refer
to the TMV3 Requirements Manual.
1. Turn on the mixer to the maximum temperature (i.e.. fully anticlockwise) and allow the
temperature to stabilize.
If the temperature is too hot or too cold, adjust as follows:
2. Use the 2.5mm hexagon key to slacken the grub screw retaining the control lever. Remove
the control lever.
3. Unscrew the hub retaining screw.
4. Push the hexagon key down through the threads and rotate the hexagon key until the
required maximum temperature is obtained at the shower. Anti-clockwise to increase the
temperature, or clockwise to decrease the temperature (1/4 turn = approximately 1°c).
5. Once the desired maximum blend temperature has been achieved, turn off the mixer.
6. Refit the hub retaining screw.
7. Locate the bearing with the lug in the 8o'clock position.
8. Align the control lever at the 6o'clock position and refit, securing with the securing screw.
9. Check that the shower temperature is correct.
10.
Fit the rubber plug to conceal the grub screw.
Version 8 12/2018
Page 14