Keys pressed
"SET" & "+" & "-" Press them together for a few moments until the display shows MA
+
Increases the frequency and rotation of the electropump
-
Decreases the frequency and rotation of the electropump
Moves on to the next item in the following menu
FP = Setting of the test frequency in manual mode (Hz) ≤ at the set FS value
UP = Display of pressure (bar)
MODE
C1 = Display of the electropump phase current (A)
rt = Setting of the direction of rotation
UF = Display of flow
ZF = Display of zero flow
MODE & -
The electropump runs at the set frequency as long as the keys are held down
MODE & - & +
The electropump remains operating at the set frequency
(for 2 seconds)
The electropump may be switched off by pressing MODE & -
SET
Press to leave manual mode
When the system is in manual mode the whole display blinks.
11.
GENERAL SYSTEM RESET
Access keys MODE & SET & + & -
To restart the appliance without disconnecting the power supply press the 4 keys simultaneously.
12.
RESTORING THE FACTORY SETTINGS
Access keys SET & + for 2 seconds when switching on
The factory settings are indicated in table no. 14 on page 36.
To reset the factory values:
Switch off the appliance, press and hold down the SET and + keys while switching on the appliance again, release
the two keys only when the letters EE appear. In this case the ACTIVE DRIVER restores the factory settings.
When it has finished setting all the parameters the ACTIVE DRIVER returns to normal operation.
In this phase, in the models in which RC is active, the motor current is set at 0 as factory
default, so when you try to start the electropump it will immediately give the error EC.
Go to the installer's display and settings menu (keys MODE & SET & - for 5 seconds ) and
set the correct motor data plate current (parameter rC as in paragraph 8.4.1.)
13.
ERROR AND STATUS CONDITIONS
The ACTIVE DRIVER is equipped with a protection system against malfunctions. If any malfunctions
occur, this is indicated on the display and, depending on the type of error, the electropump may switch
off.
In cases of blockage due to water lack (bL), blockage due to current overload in the electropump (oC),
blockage due to current overload in the output stages (oF), blockage due to direct short circuit between the
phases of the output terminal (SC) and of low line (LL) indication, you may try to exit the error conditions
by pressing the "+" and "–" keys simultaneously. If the error condition remains, you must take steps to
eliminate the cause of the malfunction.
Display indication
bL
LP
HP
LL
ot
oC
oF
SC
EC
E0...E7
F1
F3
ENGLISH
Use of the keys.
MODE & SET & + & -
Error conditions
Error and status conditions
Blockage due to water lack
Blockage due to low supply voltage
Blockage due to high rectified voltage
Low line voltage indication
Blockage due to overheating of the power stages
Blockage due to current overload in the electropump motor
Blockage due to current overload in the output stages
Blockage due to direct short circuit between the phases of the output terminal
Blockage due to incorrect setting of the rated current
Blockage due to internal error 0...7
Blockage due to input 1 status
Blockage due to input 3 status
Action
Description
34