4-noks
Elios4you Pro
5) There is never any indication on my system of power being supplied to the grid
Check that the grid CTs (yellow label) are positioned on the lines leaving the relative meter,
9
upstream of any branch made within the electrical system.
6) At night there is zero usage, whereas during the day consumption is always higher than normal
Check that the grid CTs (yellow label) are positioned on the lines leaving the relative meter,
9
upstream of any branch made within the electrical system.
Check for correct correspondence between the sequence of supply voltages connected to the
9
main switch and the sequence in which the CTs are positioned on the various conductors.
7) App shows very high levels of consumption, whereas usage by the consumer is minimal
Check that the grid CTs (yellow label) are positioned on the lines leaving the relative meter,
9
upstream of any branch made within the electrical system.
Turn the grid CTs (yellow label) about face, so that the green dot or the arrow on the inside of
9
the CTs is positioned on the opposite side to that currently in use.
Conformity
All models comply with Directives 2004/108 EC and 2006/95 EC, and with Directive
99/5 EEC. The declaration of conformity can be viewed at:
www.4-noks.com/
download.
Safety and disposal
Electrical and electronic equipment requiring sorted collection, in compliance with local
regulations on waste disposal currently in force.
Astrel Group reserves the right to change product specifications without notice.
Meaning of Elios4you Pro terminal numbers (table 3)
Terminal
Meaning
1
SIG + (CT L1 Production – white ), red wire
2
SIG + (CT L1 Production – white ), black wire
3
SIG + (CT L2 Production – white ), red wire
4
SIG + (CT L2 Production – white ), black wire
5
SIG + (CT L3 Production – white ), red wire
6
SIG + (CT L3 Production – white ), black wire
7
SIG + (CT L1 Grid – yellow), red wire
8
SIG + (CT L1 Grid – yellow), black wire
9
SIG + (CT L2 Grid – yellow), red wire
10
SIG + (CT L2 Grid – yellow), black wire
11
SIG + (CT L3 Grid – yellow), red wire
12
SIG + (CT L3 Grid – yellow), black wire
4-NOKS is a brand of ASTREL GROUP
ASTREL GROUP SRL
/
Via Isonzo, 21/E
/
34070 Mossa (GO) Italy
/
www.astrelgroup.com
/
www.4-noks.com
Installation and instruction manual
Installation diagram (fig. 2)
Grid CT (yellow label)
Green dot and direction of arrow K L
Main meter
N
toward main switch
L3
L2
L1
Terminals N, L1, L2, L3 minimum
conductor section 1.5 mm
Generic load 10A max @ 240Vac
(optional)
Do not wire
Do not wire
X
GND
Ctrl
X
X
X
X
X
X
X
IN+10 V
13
14
15
16
17
18
19
20
21
22
23
24
25
26
Relay contact N.O.
ID CODE:YYYYY
123456789XXXXX
ID Code label
N
L1
L2
L3
S
1
2
3
4
5
6
7
8
9
10
11
12
2
Production CT (white label)
Green dot and direction of arrow K L
toward main switch
L1 L2 L3 N
Main switch
L1 L2 L3 N
COMMON (alarm 2)
Alarm 2 input
COMMON (alarm 1)
Alarm 1 input
L3
L2
L1
N
+05T408110R3.0 Elios4you Pro Instruction manual IT-EN-FR-DE
Astrel Group reserves its rights to make changes or variations to its own products without any prior notice
N
Generation meter
L3
L2
L1
Consumer
/
20.12.2016
/
p. 4/8