Applicable to Models: CFD-1F, CFD-2F, CFD-3F
ColdTech® Freezer Settings
Temperature set to -4 F
Parameter
Function
E1
Lower Setpoint Limit
E2
Higher Setpoint Limit
E3
Hysteresis, temp variance
E4
Comp. start delay time
E5
Offset on room temp
E6
Offset on evap temp
F1
Max. defrost duration
F2
Defrost interval time
F3
Defrost termination temp
Key
F = Farenheit (degrees)
min. = minutes
hr. = hours
Do not change the default settings of your ColdTech unit
without consulting a qualified service technician or the
Warning:
ColdTech service department.
-10-
Set Range
-40 F ~ set temp
set temp ~ 120 F
1 ~ 18 F
0 ~ 10 min.
-5 ~ 5 F
-5 ~ 5 F
1 ~ 60 min.
0 ~ 24 hr.
32 ~ 68 F
temp = temperature
max = maximum
N/A = not applicable
Default
-10 F
20 F
10 F
3 min.
0 F
0 F
30 min.
6 hr.
68 F