Mounting dimensions are shown in Figure 2.2.2.4.

2.2.3 Mounting

While considering mounting location for the detectors, please be guided by actual national
codes and mounting rules for fire detectors - for example, by the code of practice "СП
484.1311500.2020", in particular by the requirements shown in the table 1.
Supervised Room Height, m
Up to 3.5
More than 3.5 to 6.0 inclusive
More than 6.0 to 9.0 inclusive
If it is not possible to install detectors on a flat slab, these ones can be suspended by steel ropes
(strings) or installed on walls, columns and other bearing building structures as per Clause 6.6.9 of
the code of practice "СП 484.1311500.2020".
Mounting kits MK-2 or MK-3 (supplied per a separate order) can be used for attaching the
detectors to a suspended ceiling.
To provide mechanical protection for the detector, a Protection Wire Cage can be used, which is
to be supplied separately.
For mounting the detector, the base plate supplied is to be used (see Figure 2.2.3.1).
Warning!
To install the detector into the base plate, align the guide on the detector with the
short guide on the base plate. Then turn the detector clockwise until the detector guide
is aligned with the guide 2 as shown in Figure 2.2.3.1.
Mounting and dismounting the detector shall be carried out with its power being
off.
Figure 2.2.2.4
Detection Area Radius, m
Figure 2.2.3.1
3.55
3.20
2.85
1: Base Plate
2: Alignment Guide
11