Host Communication Wiring

The MAP2 elevator control panel is equipped with an Ethernet RJ45 jack (see image below) to allow
easy connection for communication with the host.

Wiegand-Compatible Reader Wiring

The elevator reader, which is mounted in the elevator cab, can read a standard 26-bit or Cansec 37-bit
Wiegand proprietary format card or the HID Corporate 1000 format card. The MAP2 panel uses a
small 6 pin keyed connector to terminate the reader wiring. The MAP2 reader connections are labeled
below the reader connectors, as shown below. The 12 VDC power is supplied to the reader through
the reader connector. The MAP2 reader port uses an auto-resettable fuse with a 1 amp maximum
rating. A 6-conductor overall shield wire is required for proper Wiegand reader connection. See the
reader manufacturer for the wire gauge requirement for different reader distances to the control panel.
Connect elevator reader to port RD1 only.
MAP2 Panel
Connecting Wiegand-Compatible Reader
MAP2 Elevator Control
Installation Guide
This reader is mounted in the
elevator cab.
Page 16 of 16
April 2020 • Rev. 1.0