Note:
Switching hysteresis: 0.05 x (SP.Hi – SP.Lo).
6.2

Alarm

If the control function Cnt is set and the alarm function d.FnC = ON, the display blinks with a
frequency of about 2 Hz when the output is switched on (see Fig. 6.1).
6.3

Filter

Undesirable signal fluctuations can be suppressed through the adjustable filter in the
parameter td "Filter time constant" (see Fig. 6.2 and Table 7.2).
The filter time constant can be set within the range 0...10 seconds. The higher the value, the
slower the display reaction to changes of the input signal and the lower the susceptibility to
interference is. The filter is deactivated if td = 0.
6.4

Square root function

The function is intended for transmitters with the square characteristic. To enable the
function set the parameter Sqrt = ON.
6.5

Error

Table 6.1 Displayed errors
Display
Eг.1
LLLL
HHHH
akYtec GmbH · Vahrenwalder Str. 269 A · 30179 Hannover · Germany Tel.: +49 (0) 511 16 59 672-0 ·
Fig. 6.2 Filter time constant
Possible cause
Measured value error
Measured value is
below the lower limit for
the selected signal
Measured value is
above the upper limit for
the selected signal
Signal
Threshold
-
-
0-5 mA
I < -0.2 mA
0-20 mA
I < -0.2 mA
4-20 mA
I < 3.8 mA
0-10 V
U < -0.1 V
2-10 V
U < 1.5 V
0-5 mA
I > 5.5 mA
0-20 mA
I > 22 mA
4-20 mA
I > 22 mA
0-10 V
U > 11 V
Remedy
Check the input signal.
Check the sensor and
connection lines.
Contact the Technical
Support of akYtec
GmbH.
Check the input signal
Check the input signal