- ページ 10

ボイラー ADVANCE Easy Moving M-TANKのPDF 組立・使用・メンテナンスマニュアルをオンラインで閲覧またはダウンロードできます。ADVANCE Easy Moving M-TANK 17 ページ。

ADVANCE Easy Moving M-TANK 組立・使用・メンテナンスマニュアル
Motorized Tank
The operating time may also need to be changed at any time in the future to accommodate a different
type or specifi c weight of the fuel used.
When the fuel level inside the motorized warehouse decreases, the sensor located inside it (see Figure
2) will stop the engine operation, leaving the transport system in standby mode, as soon as the correct
fuel level is restored, the system will restart automatically.
10.1 Minimum level sensor calibration
The sensitivity of the minimum fuel level sensor is already calibrated, but if a new calibration is needed, proceed
as follows (see Figure 7):
• Place the sensor in front of the surface to be detected (pellets).
• Use a screwdriver with a max diameter of 3 mm.
• Rotate the potentiometer clockwise or counterclockwise for 2/3 turns until it reaches the correct activation point
(LED on).
• If turning the potentiometer the LED lights up immediately, turn it counterclockwise for about 45° and then turn it
clockwise again until it reaches the point of activation (LED on).
fi gure 5
10.2 Operational safety
There is a safety that guarantees the correct functioning of the tank, this safety acts every time for three consecutive
engine operating cycles, fuel is not sucked and therefore the dispenser remains empty.
In this case, the security interrupts the operation which is not automatically restored.
The causes of malfunction can be various, including the following:
A) lack of fuel inside the tank
B) A fuel clog has formed in the pipeline between the tank and the dispenser.
C) Pipes are not intact or there are air leaks in their fi ttings
D) The fi lter inside the dispenser is blocked
E) The dispenser exhaust door is not tightly closed during suction.
When the cause of the blockage has been removed, the light switch must be switched off for at least 3 seconds and
then turned on again (light on).
If the problem occurs frequently, it is advisable to contact the service centre.
10
fi gure 6
LED
fi gure 7
-
+
15/12/21 Rev:1.0.1