- ページ 4

コントローラー DOTECH FX3DH-00のPDF マニュアルをオンラインで閲覧またはダウンロードできます。DOTECH FX3DH-00 4 ページ。 Digital temp. & humidity controller

Alarm Operation Group
OFF
HY
AL -1
SV
PV
80
90
※ set DF to 10
OFF
ON
HY
AL-2
PV
SV
70
80
※ set DF to 10
O
N
H
Y
AL-3
PV
70
OFF
HY
AL-4
PV
70
OFF
ON
HY
AL-5
PV
70
※ set DF to 70
ON
HY
OFF
AL-6
PV
70
※ set DF to 70
SBA
Alarm Option Group
CODE
ALA
ALB
ALC
ALD
※ Reboot or push PRG button in 2 successive time when alarm output is removed.
Analog(4~20mA)Output Mode
Current value (PV) trans. output
Output
20mA
4mA
RTL
RTH
set AOM to PV (Current value)
RTL
Input PV at 4mA output.
RTH
Input PV at 20mA output.
ON
OFF
ON
HY
PV
SV
70
80
※ set DF to -10
ON
HY
SV
PV
80
90
※ set DF to -10
OFF
O
N
H
Y
SV
PV
90
80
※ set DF to 10
ON
OFF
HY
SV
PV
※ set DF to 10
90
80
OFF
HY
PV
90
※ set DF to 90
ON
PV
90
※ set DF to 90
OPERATION TITLE
General alarm
Maintain alarm
Standby alarm
Maintain & standby alarm
Dehumidification(Cooling)
proportional Control
Output
20mA
4mA
PV
ST1
ST1+DF1
set AOM to ReV (Dehumidification
(Cooling) proportional Control)
ST1
Input SV at 4mA output.
DF1
Input DF at 20mA output.
* SV : ST1~ ST2
Deviation High Limit Alarm
Output is ON when the deviation between PV value and SV value is higher
than setup value of control deviation
OFF
Deviation Low Limit Alarm
Output is ON when the deviation between PV value and SV value is lower
than setup value of control deviation.
Deviation High & Low Limit Alarm
Output is ON when the deviation between PV value and SV value is higher
or lower than setup value of control deviation .
Control deviation is set up at DF in setting 1 group.
If DF value ≤ 0, it is always OFF.
Deviation High & Low Limit Reverse Alarm
Output is OFF when the deviation between PV value and SV value is higher
or lower than setup value of control deviation .
Control deviation is set up at DF in setting 1 group.
If DF value ≤ 0, it is always OFF.
ON
Absolute Value High Limit Alarm
Output is ON when PV value is higher than or equal as control deviation
setup value. Alarm temperature is set up at DF in setting 1 group.
It works regardless of SV(Set value).
HY
OFF
Absolute Value Low Limit Alarm
Output is ON when PV value is lower than or equal as control deviation
setup value. Alarm temperature is set up at DF in setting 1 group.
It works regardless of SV(set value).
Sensor Open Wire Alarm
DESCRIPTION FOR ALARM OPTION OPERATION
Standard alarm operation without option
Maintain output ON after alarm occurs
No output at initial operation (until achieve the 1st setup value)
Execute both ALB & ALC at the same time
Humidification(Heating)
proportional Control
Output
20mA
4mA
PV
ST1-DF1
set AOM to DIR (Humidification
(Heating) proportional Control)
Input SV at 4mA output.
ST1
Input DF at 20mA output.
DF1
* DF : DF1~ DF2
* HY : HY1~ HY2
Output is ON when sensor wire is opened.
Set value(St) trans. output
Output
20mA
4mA
PV
ST1
RTL
set AOM to ST1-2 (set value)
RTL
Input SV at 4mA output.
RTH
Input SV at 20mA output.
St1~2
(SV)
RTH
4