insTall aTiOn seTup
4.1 verifying the accuracy of the connections and connecting the power supply
check the correctness of the connections in the installation!
The +14 V, C/D and GND signals are the same for all components of the installation.
Any short-circuit between them will affect all the indoor terminals, causing them not to function.
connect the power supply to the 230 V a.c. network through a 10 A automated fuse!
Optionally, the accumulator is connected to the +ACC;-ACC hubs of the SAC. V1A.DIN power supply.
Pay attention to the connection to the correct polarity of the outdoor accumulator!
check the correct functioning of the power supply:
• The measured tension at the hubs of the power supply: +14 V ⟷ GND / 13,8 ÷ 14,3 V d.c.
• Power supply signaling, according to the following table:
Signaling
S1 permanent Green
1
S2 permanent Green
S1 alternating Red / Green
2
S2 permanent Green
S1 alternating Red / Green
+ acoustic signaling
3
S2 permanent Green
S1 permanent/flashing Red
4
S2 turned off
S1 flashing Green
5
S2 turned off
4.2 programming the Tags
The Red Programming TAG contains the unique code of the installation company.
When an outdoor panel reads a Programming TAG for the first time, it is personalized with the company's unique code.
The code is permanently registered in the panel's memory and can only be erased at the producer.
The personalized panel will not accept the Programming TAGs of other installation companies.
how to program the Tags' access codes in the memory of the outdoor panel:
The door on which the lock is mounted will remain closed the entire time it takes to program the TAGs! Entering the programming mode with the
door open will erase all acces codes.
1. Use the Red Programming TAG!
The Programming mode closes automatically if the panel is idle for more than 10 seconds or imediately by using the Programming TAG once more.
2. You now have a maximum of 10 sec. for each Access TAG.
• [
] when the Access Code has been succesfully memorized,
BEEP BEEP
• [
] when the TAG's Access Code is already in the panel's memory,
BEEP
BEEP
• [
] when the panel has been idle for 10 seconds and is no longer in the Programming Mode.
BEEP
To erase all the access codes from the panel's memory:
This action cannot be undone! The panel will not recognize any Access TAG.
1. Enter the Programming Mode!
2. Operate the lock's button * for at least 6 seconds!
* If the lock does not have a button, you need to short-circuit between the BUT and LC hubs (of the outdoor panel) for at least 6 seconds.
4.3 programming the address of the additional outdoor panel
Remember:
The default address of all oudoor panels is 1.
The installation must have one outdoor panel with the adress 1. This will be the main panel.
The outdoor panels must have unique addresses within the installation.
The installation does not work if 2 panel's share the same address!
how to program the additional outdoor panel:
The door on which the lock is mounted will remain closed the entire time it takes to program the additional panel!
1. Use the Red Programming TAG on the additional panel!
The Programming mode closes automatically if the panel is idle for more than 10 seconds or imediately by using the Programming TAG once more.
2. Press any key!
[
] when the panel's address increases by +1, [
BEEP
For the following 10 seconds, the additional panel is still in the Programming Mode and you may proceed to program its Access TAGs.
Observations
The installation is ready to function.
If the audio or video communication is not functioning, check the
status of fuses Sig. 1 and Sig. 2 from the power supply.
The installation is functioning.
Charging accumulator.
The installation is functioning.
Faulty or uncharged accumulator: replace the accumulator!
The installation is functioning only on audio communication,
for a limited amount of time.
Check the power fuse from the network and fuse Sig. 3.
The installation is NOT functioning.
Shortcircuit in the installation on +14 V and/or +Uv.
Eliminate the shortcircuit and re-establish the connection!
The panel enters the Programming Mode: [
You will hear the following sounds:
(by using the Programming TAG)
Acoustic confirmation: [
The panel enters the Programming Mode: [
Network tension
230 V ± 10%
230 V ± 10%
]
BEEP BEEP
BEEEEEEP
]
BEEP
BEEP BEEP
] when the panel is bak to having address 1.
BEEP
BEEP BEEP
Tension presence: +14 V, +Uv
+14 V ⟷ GND 13,8 ÷ 14,3 V d.c.
50 Hz
+Uv ⟷ -Uv 13,5 ÷ 15,0 V d.c.
+14 V ⟷ GND 10,5 ÷ 13,8 V d.c.
NO: 0 V
+Uv ⟷ -Uv NO: 0 V
NO: 0 V
50 Hz
]
BEEP BEEP
BEEEEEEP