計測機器 Electrex NET D6のPDF インストレーション・インストラクションをオンラインで閲覧またはダウンロードできます。Electrex NET D6 4 ページ。 Energy analyzer & web data manager
Electrex NET D6 にも: インストレーション・マニュアル (4 ページ)
NOTE n.1
NET
3PH-3W-2CT 2 phases 3 wires, triangle
3PH-4W
3 phases 4 wires, Star
2PH-2W
2 phases 2 wires, biphase
1PH-2W
1 phase 2 wires, monophase
IMP/EXP
IMP = Only import, EXP = Import/Export
CT
Primary / Secondary of the current transformer (CT)
VT
Primary / Secondary of the voltage transformer (VT)
NOTE n.2
P AVG
Integration time of the average value (AVG) and peak value (MD) for
power (from 1 to 60 minutes)
I AVG
Integration time of the average value (AVG) and peak value (MD) for
current (from 1 to 60 minutes)
NOTE n.3
MODE
SLAVE
RS485 port set as Slave for the network.
MASTER
RS485 port set as Master for the network.
TOUT
Predetermined time in which a given operation must be
terminated
RETR
Number of communication attempts on the RS485 port
NOTE n.4
NOTE n.5
DHCP
Enable / Disable the search for a DHCP server in the network
IP
IP address of the network interface
NETM
Subnet mask: defi nes the belonging range of a host within an IP
subnetwork
GWAY
IP address of the gateway
NOTE n.6
DEF
Select the network interface to be used as default for communication.
ETH
Enable / Disable the Ethernet port (LAN)
WIFI
Enable / Disable the Wi-Fi port
NOTE n.7
DIM
Enable / Disable dimming of the display
TIME
Time in seconds after which the display luminosity is reduced. (With DIM
enabled)
LIGHT
Luminosity level of the display
PULSE
Enable / Disable the fl ashing of the sine wave symbol
Electrex logo.
MESSAGE "CFG ERROR"
During the set up operation a "CFG ERROR" message could appear. This means that
some wrong parameters are inserted.
CFG ERROR
Digital Inputs
Supply voltage (external):
Current consumption:
Max. count frequency
N.B. For gas meters a galvanic separation is
needed per ATEX standards
INPUT & OUTPUT CONNECTION EXAMPLE
light near the
DIP FUNCTION
1 Line termination resistance (120 Ohm)
2 Fail safe resistance B (-)
3 Fail safe resistance A (+)
4 Not used
* with RS-485 Master PUK activated
The instrument is equipped with a Ethernet Lan 10/100 Auto-MDI/MDIX port.
For the connection can be used a data cable straight or crossover.
Note: the port is not a PoE (Power over Ethernet = device power supply via the Lan port)
type. The connection of the device to a PoE port is anyway accepted. The power supply
anyway must be always provided by an external power supplier.
The ExpBus port, confi gurable via Ethernet port on web pages:
- uses a multicast communication rated at 250kb/sec with collision management
- max cable length : 10 meters
- manages up to 16 modules (but technically can manage up to 126)
- uses the UTP cable, 4 wires used:
2 for the power supply at 9 Vdc
2 for the bidirectional communication
The modules will also power supply the ExpBus port
The cable must be connected in in-out modality (multidrop) as per the RS485 Bus.
INPUT & OUTPUT CONNECTION
12
C
2
1
DI (-)
11
10
11
12
AUX
10
!
DI (+)
IN/OUT
Digital outputs (optocoupled NPN
transistor type for DIN 43864)
from 10 to 30
Vdc
Maximum applicable voltage:
from 2 to 10mA
Maximum switchable current:
10 or 100Hz
FROM:
- TRASDUCER WITH FREE POTENTIAL CONTACT
- UTILITY METER
- SWITCH STATUS
- ALARM STATUS
S1 S2 S1 S2 S1 S2
B A 10 11 12
I1
I2
I3
CURRENT INPUTS
RS-485
IN/OUT
VOLTAGE INPUTS
POWER
AUX
SUPPLY
IN/OUT
V1
V2
V3
N
17
18
19 20
DIP-SWITCH CONFIGURATION
LAN 10/100 ETHERNET PORT
EXPBUS
ETHERNET
EXPBUS PORT
21
AUX
DO2
!
IN/OUT
19
20
21
20
DO1
19
C
1
2
Common
27 Vdc
27 mA
NC
NC
C
C
AUX
NO
NO
N L
230 V~
R
R
e
e
l
l
24V =
a
a
- +
y
y
21
SLAVE
MASTER *
OFF
ON
OFF
ON
OFF
ON
OFF
OFF
ON
ON
1
2 3 4
1
2 3 4