- ページ 19

アクセサリー Baumer O200のPDF 取扱説明書をオンラインで閲覧またはダウンロードできます。Baumer O200 34 ページ。 Sensors with io-link

Baumer O200 取扱説明書
Parameter name
Response Delay.SSC4 Time
Release Delay.SSC4 Time
Minimum Pulse Duration.SSC4 Time
4.3.4.2 SSC4 Behavior
By enabling autoreset, a full-featured counter being able to count lot sizes can be created without any need
of a manual reset.
Timefilters like Response Delay can help to optimize the timing of the execution of a subsequent actor.
Figure 21 illustrates the behavior of SSC4 using different setting. SSC4 source is hereby the switchcounter
of SSC1.
Figure 21 Behavior SSC4/Counter: Single-Point or Window, Autoreset enabled or disabled
en_BA_O200_IO-Link_V1.docx
15.08.2018/
Short Description
Sets the response delay time,
Available for SSC1, SSC2, SSC3
and SSC4
Sets the release delay time,
Available for SSC1, SSC2, SSC3
and SSC4
Sets the response delay time,
Available for SSC1, SSC2 , SSC3
and SSC4
19/34
Rights
Unit / Allowed
values
0 to 60'000 ms
rw
0 to 60'000 ms
rw
rw
0 to 60'000 ms
Baumer Electric AG
Frauenfeld, Switzerland