Thermal behavior

Standard surrounding air temperature is up to 50 °C. For ambient temperature over this limit, the output current
is reduced by 2.5 % per °C. Maximum temperature is 70 °C. At the temperature 70°C the output current will be
50% of nominal current. The charger does not switch off in case of ambient temperature above 70°C or in case
of thermal overload. The device is protected for over temperature conditions "worst case". In this situation the
device shut-down the output and automatically restart when internal temperature fall down into limits.

Rail mounting

The charger module must have a minimum vertical and horizontal distance of 10 cm to the other used DIN rail
modules in order to guarantee sufficient auto convection for proper cooling.
It is allowed to install the unit only in horizontal positioning (DIN rail horizontal). Maximal inclination is +/- 5 %.
IMPORTANT: Depending on the ambient temperature and load of the charger, the temperature of
the housing can become very high!
1
Recovery state is not available at the types of chargers with power supply mode always on. Recovery state
will not be triggered at this particular product.
2
Recovery state is not available at the types of chargers with power supply mode always on. Recovery state
will not be triggered at this particular product.