- ページ 8

コントロールパネル Advanced MxPro 4 4100SのPDF マニュアルをオンラインで閲覧またはダウンロードできます。Advanced MxPro 4 4100S 12 ページ。

2.3 Battery Installation

The diagram opposite shows the
recommended location and orientation
for the 7AH batteries within the panel.
For battery sizes greater than 7AH, the
batteries must be installed in a separate
enclosure suitable for fire protection use
with wiring connected to the panel
through rigid conduit.
Replacement Fuses
FS1
T5A
125V Anti-Surge
FS2
T5A
125V Anti-Surge

2.4 Wiring Installation

Refer to Manual 680-014 for further information.

2.5 Battery Standby Calculation Chart

Use the following charts and associated notes to calculate the size of the batteries required to ensure operation
of the installation in the event of AC Mains power failure.
Equipment
Mx-4100S
Sensor / Loop Current
Mxp-024 LED Indicator – 20 Zone
Auxiliary Supply Output
Sounder Output A
Sounder Output B
Total
3
Use the detector manufacturers' technical information to calculate the load on the loop for both the quiescent condition and fire alarm
condition for all loop devices. By default, a maximum of 5 detector / call point LED indicators will be turned on in a fire alarm condition. (This
number can be changed via the PC Programming Tool).
4
The calculated loop loading must be multiplied by a factor of 1.25 to calculate the actual current draw from the batteries. This is to take into
account voltage conversion and conversion efficiency in generating the supply for the loop.
5
Refer to separate data sheets for the additional modules that can be powered from the panel AUX Output to determine the AUX loading
currents. For example, the modules can include Modem, Sounder Splitter, Routing Interface, etc. The sum of all these additional currents
should be entered in these fields.
6
The alarm load should be doubled to allow for changes in battery efficiency for loads in excess of the recommended C/20 discharge rate.
The total load calculated should be multiplied by a de-rating factor of 1.25 to allow for changes in battery efficiency over time. The above
calculation is in accordance with the recommendations in BS5839-1: 2002.
8
I (A)
0.115
3
0.003
5
Quiescent Load
Quiescent Load
x
Total
1.0
= 0.115
0.225
4
1.25
=
1.0
=
0.012
1.0
=
=
x 24 hr =
Ahr
Ahr
x 48 hr =
x 72 hr =
Ahr
(carry forward)
Total Load (Quiescent + Alarm) =
6
x 1.25
(Battery De-rating factor) =
Fire Alarm Load
I (A)
x
Total
1.0
= 0.225
1.25
=
1.0
=
1.0
=
1.0
=
1.0
=
Alarm Load
=
6
x 2
x 0.5 hr =
Ahr
Ahr
+
Ahr
Ahr
www.advancedco.com