2.1
Install condensing unit
• Level unit
• Securely attach base of unit using holes found in base plate
2.2
Rack system
• 1412N not compatible with rack system. Consult Technical Service.
2.3
Electrical requirements
• Electrical disconnects required
• Electrical disconnects installed in accordance with NEC and local electrical codes
Minimum circuit ampacity
Maximum overcurrent protection
Outdoor condensing unit operating limits
(air temperature)
REMOTE CONDENSING UNIT
Condenser installation
CAUTION
Horizon Elite 1412 series
three phase – 12A
three phase – 20A
min –20 F (–29 C)
max 120 F (49 C)
2