3.3 Input Configuration

Point Options for Fire Action
Input configuration is performed along the same line as configuring any loop device.
Setting the "Input Action" to "No Action" has the following impact:
-
Input is disabled at the hardware end (overall power consumption is reduced)
-
End of Line resistors are not required for unused inputs.
Each Zone circuit can be individually configured to treat short circuits as activating/qualifying conditions; this is
done via the "Short Circuit Qualifies Action" checkbox.
Each Zone circuit can be individually configured to operate in Intrinsically Safe mode; which is intended for use
only with an appropriate I.S Barrier and I.S. Devices.
Each zone can be configured for Alarm Verification by setting the "Comfirmation Filter" option. To get this
option the "Confirmation Filter" must first be enabled under "Panel Details→General Options"
Each Zone can be configure for Latching or non latching operation. Non Latching zones will reassert an active
condition 10 seconds after activation. The default sequence is as follows:
Activation →10s Reassert Delay → 2s Reset → 5s Zone Evaluation Inhibit → Full Monitoring
The Zone EOL selection is an option common to all the zones in a card, setting a zone to 6K8 will change the
setting on all other zones for that card.