Outdoor Unit Installation
Guideline
• Where a wall or other obstacle is in the path of outdoor unit's intake or exhaust airflow, follow the installation guidelines below.
• For any of the below installation patterns, the wall height on the exhaust side should be 1200mm or less.
Wall facing one side
More than 100
Selecting a Location for Installation of
the Indoor Units
• The maximum allowable length of refrigerant piping, and the maximum allowable height difference between the outdoor and
indoor units, are listed below.
(The shorter the refrigerant piping, the better the performance. Connect so that the piping is as short as possible. Shortest allow-
able length per room is 3m.)
Outdoor unit capacity class
Piping to each indoor unit
Total length of piping between all units
Level
Level
difference:
difference:
7.5m max.
15m max.
(Heat pump
unit only)
If the outdoor unit is positioned higher than the
indoor units.
5
More than 350
1200
or less
Side view
Indoor Unit
Outdoor Unit
Walls facing two sides
More
than 100
More than 50
Walls facing three sides
More than 50
Top view
2MXS52, 2AMX52, 3MXS52, 3AMX52, 3MKS50, 4MKS58
25m max.
50m max.
Level
difference:
15m max.
Level
difference:
7.5m max.
(Heat pump
unit only)
If the outdoor unit is positioned otherwise.
(If lower than one or more indoor units)
More than 350
More than 50
Top view
More than 100
More than 350
Unit: mm
Outdoor Unit
Indoor Unit