7.3.1. Button name and function
7.3.2. Checking the function settings
Press and hold the "MANUAL AUTO" button on the indoor unit for 3 seconds to check the
function settings. It is necessary to disconnect the power in order to return to normal op-
eration mode.
(1) Indoor unit and refrigerant address indication
Indication pattern
Indicator name
OPERATION indicator lamp
(Green)
TIMER indicator lamp (Orange)
FILTER indicator lamp (Red)
• Indoor unit address example
(Example) ADDRESS : 24
OPERATION
ON
indicator lamp
(Green)
OFF
TIMER
ON
indicator lamp
0.5s 0.5s 0.5s 0.5s
OFF
(Orange)
ON
FILTER
0.5s 0.5s 0.5s 0.5s 0.5s 0.5s 0.5s 0.5s
indicator
OFF
lamp (Red)
• Refrigerant address example
(Example) ADDRESS : 30
OPERATION
ON
indicator lamp
1.0s
(Green)
OFF
TIMER
ON
0.5s 0.5s 0.5s 0.5s 0.5s 0.5s
indicator lamp
OFF
(Orange)
ON
FILTER
indicator lamp
OFF
(Red)
• Setting details
Function number
01
Indoor unit address
02
Refrigeration address
For use with a remote controller, set all rotary switches to 0, and refer to "7.1. Setting the
address" for details.
All switches are set to 0 at the factory.
(2) Others
Indication pattern
Indicator Name
OPERATION indicator lamp (Green)
TIMER indicator lamp (Orange)
FILTER indicator lamp (Red)
(Example) Function : 31, Setting number : 2
OPERATION
ON
indicator lamp
0.5s
0.5s
(Green)
OFF
TIMER
ON
indicator lamp
0.5s 0.5s
(Orange)
OFF
ON
FILTER
0.5s
0.5s
indicator
OFF
lamp (Red)
En-13
OPERATION indicator lamp (Green)
TIMER indicator lamp (Orange)
FILTER indicator lamp (Red)
MANUAL AUTO button
Indication pattern
Indoor unit address
Refrigerant address
ON
Flash (1.0s ON/1.0s OFF)
Address: tens place (0.5s ON/0.5s OFF)
Address: ones place (0.5s ON/0.5s OFF)
1 cycle 12 sec
ON
10 sec
8 sec
1 cycle 12 sec
1.0s
1.0s
1.0s
1.0s
1.0s
9 sec
OFF
Item
Setting number
00 to 63
00 to 99
Indication pattern
Function number; tens place (0.5s ON/0.5s OFF)
Function number; ones place (0.5s ON/0.5s OFF)
Setting number: (0 to 9) (0.5s ON/0.5s OFF)
1 cycle 12 sec
0.5s
0.5s 0.5s 0.5s
9 sec
11 sec
10 sec
0.5s
0.5s
8. MOUNT THE COVER PLATE AND THE INTAKE
GRILLE

8.1. Handling for the pipe take-off part

When the pipe is pulled out in the direction shown in the fi gure below, cover the take-off
part with material (putty or the like) that will block it off.
UNDER CEILING TYPE

8.2. Mount the cover plate (Right)

(1) Cut a pipe exit hole in the right plate. This is only when the pipe exits from the right
side. (This operation is not required when the protrusion is on the top or rear.)
(2) Join the cover plates (right) and mount with screws.
1.0s

8.3. Mount the cover plate (Left)

(1) Join the cover plates (left) and mount with screws.
FLOOR CONSOLE TYPE
Top
Rear
Right
Cover plate (Right) (Accessories)
Tapping screw (M4 × 10 mm)
(Accessories)
Cover plate (Left)
(Accessories)
Tapping screw (M4 × 10 mm)
(Accessories)