- ページ 13
エアコン AirStage ARUH60RLAVのPDF インストレーション・マニュアルをオンラインで閲覧またはダウンロードできます。AirStage ARUH60RLAV 15 ページ。 Indoor unit (duct type)
] 1
6.7. IR receiver unit (Optional parts)
• For the installation method, please refer to the INSTALLATION MANUAL of IR receiver
unit.
Connection methods
• Connection terminals
Controller PCB
• Wiring arrangement
Controller PCB
Binder clamp
Connecting
cable(s)
*Accessories of IR receiver unit
IR receiver unit terminal (CN13)
Cable
clamp
Binder *
7. FIELD SETTING
There are 3 methods for address setting by FIELD SETTING as follows.
Set by either of the methods.
Each setting method is described (1) to (3) below.
(1) IU AD, REF AD SW settings .............. This section (7.1. Setting the address)
(2) Remote controller settings ............... Refer to the wired or wireless remote controller
(3) Automatic address settings ............. Refer to the outdoor unit manual for detailed
Be sure to turn OFF the power before performing the fi eld setting.
] 1
7.1. Setting the address
Manual address setting method
• The indoor unit address and the refrigerant circuit address can also be set up through
the wireless remote controller
Use an insulated screwdriver to set the dip switches.
Dip switch
"SET3"
Rotary switch
Example: "0"
Rotary switch
Example: "0"
Setting
Setting
range
Indoor unit
Setting
0 to 63
address
example
2
Refrigerant
Setting
circuit
0 to 99
example
address
63
(1) Indoor unit address
Rotary switch (IU AD × 1)......Factory setting "0"
Rotary switch (IU AD × 10)....Factory setting "0"
When connecting multiple indoor units to 1 refrigerant system, set the address at IU
AD SW as shown in the Table A.
(2) Refrigerant circuit address
Rotary switch (REF AD × 1)......Factory setting "0"
Rotary switch (REF AD × 10)....Factory setting "0"
In the case of multiple refrigerant systems, set REF AD SW as shown in the Table A
for each refrigerant system.
Set to the same refrigerant circuit address as the outdoor unit.
manual for detailed setting information. (Set IU
AD, REF AD SW to 0)
setting information. (Set IU AD, REF AD SW to 0)
CAUTION
CAUTION
SW
SW
SW
SW
1
2
3
4
Type of switch
IU AD × 10
IU AD × 1
REF AD × 10
REF AD × 1
En-12