- ページ 8
エアコン AirStage ASUB18RLAVのPDF インストレーション・マニュアルをオンラインで閲覧またはダウンロードできます。AirStage ASUB18RLAV 17 ページ。 Indoor unit (wall mounted type)
AirStage ASUB18RLAV にも: 取扱説明書 (8 ページ)
A. For solid core wiring
(1) To connect the electrical terminal, follow the below diagram and connect after looping
it around the end of the cable.
(2) Use the specifi ed cables, connect them securely, and fasten them so that there is no
stress placed on the terminals.
(3) Use an appropriate screwdriver to tighten the terminal screws.
Do not use a screwdriver that is too small, otherwise, the screw heads may be
damaged and prevent the screws from being properly tightened.
(4) Do not tighten the terminal screws too much, otherwise, the screws may break.
(5) See the table for the terminal screw tightening torques.
(6) Please do not fi x 2 power supply cables with 1 screw.
Strip 31/32 in.
(25 mm)
Screw with
special washer
Cable
Cable end (Loop)
Terminal block
When using solid core cables, do not use the attached ring terminal. If you use the
solid core cables with the ring terminal, the ring terminal's pressure bonding may
malfunction and cause the cables to abnormally heat up.
B. For strand wiring
(1) Use ring terminals with insulating sleeves as shown in the fi gure below to connect to
the terminal block.
(2) Securely clamp the ring terminals to the cables using an appropriate tool so that the
cables do not come loose.
(3) Use the specifi ed cables, connect them securely, and fasten them so that there is no
stress placed on the terminals.
(4) Use an appropriate screwdriver to tighten the terminal screws.
Do not use a screwdriver that is too small, otherwise, the screw heads may be
damaged and prevent the screws from being properly tightened.
(5) Do not tighten the terminal screws too much, otherwise, the screws may break.
(6) See the table for the terminal screw tightening torques.
(7) Please do not fi x 2 power supply cables with 1 screw.
Strip 13/32 in.
(10 mm)
Screw with
special washer
Cable
Ring terminal
Terminal block
Use ring terminals and tighten the terminal screws to the specifi ed torques, otherwise,
abnormal overheating may be produced and possibly cause heavy damage inside
the unit.
Terminal number
M4 screw
(Power supply/Change: L1, L2 (N), GND)
En-7
Loop
Screw with
special washer
Cable end (Loop)
Cable
WARNING
Ring terminal
Sleeve
Screw with
special washer
Ring terminal
Cable
WARNING
Tightening torque
11 to 16 Ibf·in
(1.2 to 1.8 N·m)
6.3.2. Transmission cable
Shielded wire
(no fi lm)
• Connect transmission cables as shown in Fig. B.
• When the 2 cables are attached.
Fig. B
GOOD
Different diameter
Tighten the terminal screws to the specifi ed torques, otherwise, abnormal overheating
may be produced and possibly cause heavy damage inside the unit.
Terminal number
M3 screw
(Transmission/X1, X2)
To peel the fi lm from the lead cable, use a dedicated tool that will not damage the
conductor cable.
When installing a screw on the terminal block, do not cut the cable by overtightening
the screw. On the other hand, an under tightened screw can cause faulty contact,
which will lead to a communication failure.
Remove it with the following sequence in case of the state with the grille.
6.3.3. Remote controller cable
Remote controller cable modifi cation.
(1) Use a tool to cut off the terminal on the end of the remote controller cable, and then
remove the insulation from the cut end of the cable.
(2) Connect the remote control cable with connecting wire with solder.
Important : Be sure to insulate the connection between the cables.
Red
Remote
controller
cable
1-3/16 in. (30 mm)
1-3/8 in. (35 mm)
PROHIBITED
Connect to 1 side
WARNING
Tightening torque
4.4 to 5.3 Ibf·in
(0.5 to 0.6 N·m)
CAUTION
Connecting wire
(Accessories)
White
Black
White
Red
Insulated connection
Black
Remote controller cable