- ページ 3
リモコン AirStage UTY-DCGYのPDF インストレーション・マニュアルをオンラインで閲覧またはダウンロードできます。AirStage UTY-DCGY 11 ページ。 Central remote controller
AirStage UTY-DCGY にも: インストレーション・マニュアル (9 ページ)
Name and Shape
Q'ty
Installation
manual
1
Operating
manual
1
CD-ROM
1
Holder
1
(Set)
One touch bush
2
Connection cable
1
Screw (M4 x 20 mm)
8
Binder
4
31
ELECTRICAL REQUIREMENT
When connecting the Central remote controller, use the
following wiring.
Use
Size
Max.1.25 mm
(16AWG)
Power supply
cable
Min.0.5 mm
(20AWG)
Transmission
0.33mm
cable
(22AWG)
External input/
0.33mm
output cable
(22AWG)
Use
1Φ 50/60Hz 100-240V
Power supply
2 wire + earth (ground)
cable
(Always earth (ground) the unit)
Transmission
L
W
ON
ORKS
cable
compatible cable
External input/
Use cable in accordance with local
output cable
rules for cable
*
L
W
is registered trademark of Echelon Corporation
ON
ORKS
in the United States and other countries.
Fuse capacity
Application
This manual
Instruction book for
operation
Include the operating
manual for Central
remote controller
For power supply unit
installation (Used for
separate type)
For protection of power
supply unit cable
For power supply unit
connection
For Central remote
controller installation
Prevents dropping off
of the cable
Wire type
2
Type60245 IEC57
or equivalent
2
22AWG lEVEl 4
(NEMA) non-polar 2
2
core, twisted pair solid
core diameter 0.65mm
(1/32 in.)
2 core, twisted pair
2
(Max.cable length :
25m (82ft.)
Remark
5 A
41
SELECTING AN INSTALLATION LOCATION
41 11
Dimensions
(1)
Control unit
162(6-3/8)
Front view
118(4-21/32)
Rear view
(2)
Power supply unit
99 (3-29/32)
(1-13/16) (1-13/16)
46
46
2-φ5
5
(3/16)
135 (5-5/16)
Unit: mm (in.)
25.7(1)
Side view
Unit: mm (in.)
29 (1-5/32)
(3/16)
39.2
(1-17/32)
En-2