3.1.2 TEMPERATURE SETTING

Water temperature is set by turning the thermostat knob. The desired symbol is adjusted against the fixed
point on the control panel (Figure 9).
Upper temperature range
(about 80°C)
Lower temperature range
(about 5°C)
Fixed point on the control
panel
pevný bod na ovládacím
Adjusting the thermostat selector at the left backstop does not mean permanent shutoff of
panelu
the heating element. When the storage tank is in use without blocking the daily rate, we do
not recommend the temperature to be set above 65°C. The maximum value to select is „55".
teplota „proti zamrznutí"
(kolem 8°C)

4 IMPORTANT NOTICES

4.1 INSTALLATION REGULATIONS

Check and exchange the Mg anode regularly.
-
No stop valves can be put between the storage tank and the safety valve.
-
If the overpressure in the eater main exceeds 0.6 MPa, a reduction valve must be mounted
-
before the safety valve.
All outlets of hot water must be equipped with a combination faucet.
-
Before filling the storage tank with water for the first time, it is recommended to fasten the
-
flange connection nuts of the tank.
It is not allowed to handle the thermostat, aside from temperature resetting with a control
-
button.
All electric installation handling, setting, and regulation feature exchange, may only be
-
implemented by a service company.
Figure 9
„Ideal" temperature (about
55°C)
„Anti-freezing"
temperature (about 8°C)