Module Type F:
Module Type T:
Module Type S:
Output Modules
times less than ten seconds will drastically shorten
relay life and in no case should the cycle time be set to
zero (60 millisecond time base). Normally open
contacts are provided for both heating or cooling use.
NOTE: Do not use this output module with mechanical
contactors because they generate an excessive EMI
field which can lnterfere with other controllers. Instead
we recommend "T" output modules for this applicatlon.
mA output module can deliver full output to
This 4-20
loads having an input Impedance of 500 OHMS or less.
The cycle time setting must be ZERO for smooth
current output.
A push-on terminal is utilized as a return for ground
currents of the milliamp source. It is connected
Internally to the mating lug on the heatsink. To avoid
ground loops, drive floating (ungrounded) loads or use
isolated thermocouples.
This solid state relay is capable of 1 AMP at
120/240Vac. It is zero voltage switched and optically
isolated from the drive signal. With it, resistive loads
up to 120 watts at 120Vac and 240 watts at 240Vac
may be controlled directly. Using direct control there
is no lower limit on the cycle time setting (down to
60 milliseconds).
Larger loads may be controlled utilizing an external
contactor. In this case, It is advisable to use cycle
settings of ten seconds or greater to minimize
contactor wear. External suppresslon of the contactor
is advisable if EMI becomes a problem.
Similar to F, but pulsed 20V/20mA DC output for
driving solid state relays. Up to 6 (series input
connected) solid state relays can be used. Cycling
time (HC) can be set to optimize the load response
time requirements without sacrificing relay life.