ELECTRIC SHOCK HAZARD. Disconnect main electrical
power to the humidifier at the circuit breaker and drain the
water from unit before servicing. Hot surface inside.
• Service should be performed by an HVAC technician.
• Use only genuine replacement parts.
INSPECT HUMIDIFIER WHEN SERVICING
• Replace canister and O-ring annually or when "Service" light
turns on
• Clean drain valve and fill valve screen annually
• Replace electrode wires every 3 years or as needed (see step
3 of CANISTER REPLACEMENT AND DRAIN VALVE SERVICE)
SERVICE SHUTDOWN PROCEDURE
1. Press On/Off button to turn humidifier off (see FIGURE 1).
2. Allow humidifier to drain.
3. When the green Drain light (see FIGURE 1) stops flashing,
disconnect main electrical power to humidifier at the circuit
breaker.
4. Allow the unit to cool.
5. Shut off water supply to unit.
FIGURE 1 – STEAM HUMIDIFIER
1
On/Off button
and light
2
Drain light
3
Front panel
4
Side panel
5
Service light
WARNING
NOTICE
MAINTENANCE INSTRUCTIONS
Series AS35
Steam Humidifier
CANISTER REPLACEMENT AND DRAIN VALVE SERVICE
1. Remove front panel (see FIGURE 1).
2. Pull three wires off posts on top of canister (two electrode
wires and one water level probe wire, shown in FIGURE 2).
3. Inspect the two electrode wires (see ELECTRODE WIRE
REPLACEMENT section for detailed instructions).
Replace them if they are:
• Not tightly fitting
• Damaged
• Over 3 years old or age is unknown
• Have D shaped connectors (see FIGURE 3A)
FIGURE 2 – ELECTRODE LOCATION
WATER LEVEL
PROBE
ELECTRODE
POST
FIGURE 3A –
"D" SHAPED CONNECTOR
3
4
1
2
5
CANISTER ELECTRODES
J8
J10
90-2352
FIGURE 3B –
"O" SHAPED CONNECTOR
90-2736