When burner in operation, combustion is severe, so the burner must be fixed. Hoses or cables in area
of the combustion system must be suitable for high temperature, to prevent high temperature failure
or cause safety accidents. Burners should be periodically inspected and cleaned. Copper wire brush
may be used, if necessary, to clean burner head. The burner system should be checked twice a year
for safety operation.
Burner commissioning shall take care of ignition position, minimum and maximum output position.
Following interlocks will cause emergency stop, including gas low pressure, high pressure or low
combustion air pressure, as well as emergency stop is trigged, the main power is out, UV signal failure
or kiln safety conditions (such as high temperature limit, flue system opening, etc.) will cause the
burner lockout. Users need to know the maintenance interval recommended by the manufacturer
and the interval specified by national laws, whichever is shorter.
4. Fuel Information
The following table shows that the combustion involves common gas properties, and the operators
should strictly abide by the safety regulations. Information is provided by the fuel supplier.
Lower Calorific value
O
Composition
Reference conditions
5.
Brief introduction
FFO57 series oxygen-natural gas burner is a product developed by Anderson Thermal Solutions
(Suzhou) Co., Ltd. for reflective furnace copper smelting, suitable for pure oxygen-natural gas copper
combustion control system.
The FFO57 series oxygen-natural gas burner is rated at 2,000 KW. The burner adopts a highly
integrated design, the ignition burner, spark plug, UV design into one, reducing the installation work.
The oxygen of the FFO57 series of oxygen-natural gas burner adopts a graded design to achieve the
best performance of the burner through professional adjustment.
The FFO57 Series oxygen-gas burner is equipped with heat resistant stainless steel and quick
disassembly joints with a typical length of 800mm. To extend the service life of the sleeve and burner,
Anderson strongly recommends cooling air with a flow rate of 30 to 60 Nm
Anderson Thermal Soluions(Suzhou)Co., Ltd
Fuel
-requirement
2
Anderson Thermal Solutions – FFO57 Operation Manual
Natural gas
H
=35,900 [kJ/m
U
2.03 O
m³/ NG m³
2
>98% CH
4
1, 013.25 mbar, 0°C
2
3
]
3
/h.