Parameter code (1 byte)
0x0B
NOTE
The index of counter 1 can be changed to any value in the range of 0 to 4294967295.
Parameter code (3 bytes)
C1050Axxxxxxxx
EXAMPLE
If you want to set the index of counter 1 to 1000, you have to send in Downlink the command C1050A000003E8 (because 1000
= 3E8 in hexadecimal).
Parameter code (1 byte)
0x1E
Internal resistance of inputs (CPT1+ and IN2+)
Parameter value (1 byte)
The possible values are:
0x00 = high impedance (factory setting)
0x01 = pull-up
0x02 = pull-down
Meter 1 settings
Parameter value (4 bytes)
For xxxxxxxx (in hexadecimal):
0x00000000
to
0xFFFFFFFF
Bounce time
Parameter value (1 byte)
Value in milliseconds, between 5 and 255.
Factory setting: 50ms
Product activation
Parameter code (2 bytes)
0x010B
ATIM_ACW-MR1_UG_EN_V1.6