Two Stall Installations
3.8L = Two Stall Urinal
For two stall installations the outlet valve must first be configured by following the
conversion instructions adjacent.
The water level in the cistern must then be set to the "WL" mark, using the float
adjustment screw located on the side of the inlet valve.
The pneumatic tube must be connected to the full flush position.
= Full Flush Position
45mm
335mm
access panel
centre line
copper pipe (supplied)
400mm - 420mm
Frame
to
Reducer to Ø40
Ø20 sparge pipe
600mm
Finished Floor Level
Refer to specifications of the selected urinal.
Blank Access Panel
NOTE:
When installing the
Remote Mounting Box in
this position, please refer
to the 'Installation Note' on
page 5
Single Remote Button
Centre Line Button
(standard mounting)
Datum
950mm
Recommended
Flush Volume & Stall Setup
Configuring Flush Volume
1
Remove Outlet Valve, refer to page 17.
2
Bucket
Using a screw driver lever the bucket
hangers over the hooks, allowing it to sit
level with the 3.8L mark on the valve.
3
Replace parts back into Cistern.
4
Set Water Level using the adjustment
screw.
5
.
The Water Level should be set to
the "WL" mark on the inside of the
cistern.
Adjustment
Screw