INSTALLATION AND OPERATION MANUAL
FIGURE 7 – CONTACT CLOSURE PIN-OUT
RJ-45 PORTS
The ports are located on the front panel of each unit
VIEW INSIDE RJ-45 PORT
RJ-45 BREAK-OUT KIT (SOLD SEPARATELY)
Screw Number Corresponds to RJ-45 Port Pin Number
Link Loss:
The alarm inputs on one end are transferred to the outputs on the receiving end of the link. A closed contact
on the input causes a closed circuit on the opposing output (i.e., relay turned on). If the RS-422 serial data
link is broken or corrupt the outputs will remain in their last known good state.
Power-On State:
At power-on all alarm outputs will be open (i.e. off), they will remain in this state until a valid link is
established, after which they will then track the inputs from units with the same address.
TECH SUPPORT: 1.888.678.9427
CONTACT INPUT PORT
PIN # Wire Color
Connections
1
Blue
IN 1,5,9,13,17,21
2
Orange
IN 1,5,9,13,17,21
3
Black
IN 2,6,10,14,18,22
4
Red
IN 2,6,10,14,18,22
5
Green
IN 3,7,11,15,19,23
6
Yellow
IN 3,7,11,15,19,23
7
Brown
IN 4,8,12,16,20,24
8
White
IN 4,8,12,16,20,24
CONTACT OUTPUT PORT
PIN # Wire Color
Connections
1
Blue
OUT 1,5,9,13,17,21
2
Orange
OUT 1,5,9,13,17,21
3
Black
OUT 2,6,10,14,18,22
4
Red
OUT 2,6,10,14,18,22
5
Green
OUT 3,7,11,15,19,23
6
Yellow
OUT 3,7,11,15,19,23
7
Brown
OUT 4,8,12,16,20,24
8
White
OUT 4,8,12,16,20,24
FDC24NL[SFP] SERIES
Polarity
+
+
+
+
Polarity
+
+
+
+
INS_FDC24NL[SFP]_REV–
12/29/11