水ポンプ Compac Master MMR400-80SのPDF インストールとセットアップの説明をオンラインで閲覧またはダウンロードできます。Compac Master MMR400-80S 18 ページ。
Optional Flexi Coupling for 80 lpm Inlet
Static Electricity Precautions
3.
Electronic components used are sensitive to static. Please take anti-static precautions.
An anti-static wrist strap should be worn and connected correctly when working on any
electronic equipment. If an anti-static wrist strap is unavailable, or in an emergency, hold onto
an earthed part of the pump/dispenser frame whilst working on the equipment. This is not a
recommended alternative to wearing an anti-static wrist strap.
Note: Compac Industries Limited reserves the right to refuse to accept any circuit
boards returned, if proper anti-static precautions have not been taken.
Pre-installation Check
4.
Once the pump is received on site, check that no damage has occurred while in transit – in
particular, damage to electronics due to vibration or jarring. All terminals and plugs should be
checked, including IC chips, to ensure they are securely in place.
5.
Installation
Installation should be in accordance with local regulations.
The dispensing equipment shall be installed to prevent the delivery hose from contacting the
ground when not in use.
Where local regulations require a sump to be fitted:
a. Sumps must be provided at all dispenser installations with secondary containment
pipework and at all new installations; and
b. at all sites with sumps, dispensers should be installed with a liquid level detection device
fitted in the sump that will raise an alarm if liquid is detected in the base of the sump.
Important Note: Compac 400 litre per minute high flow dispensers do not have an internal
filtering system fitted at the factory. It is the customer and/or installers responsibility to ensure
the fuel supplied to the 400 lpm side of the dispenser is clean and free from any dirt, debris or
metal particles that could damage the meter or hydraulic components. A 10 micron filter is
recommended. Compac does not warranty the meter or hydraulic components for damage
caused by contaminated fuel supply.