- ページ 2

リレー Compact Electric CDMR-62のPDF ユーザーマニュアルをオンラインで閲覧またはダウンロードできます。Compact Electric CDMR-62 13 ページ。 Digital line monitoring relay, 3x100v/57v ac

Compact Electric CDMR-62 ユーザーマニュアル
Grid monitoring relay CDMR-62
Technical data
Measuring circuit:
Rated voltage U
.....................
n
Measuring range ......................... :
Overload resistance .................... :
Input resistors ............................. :
Frequency range ......................... :
Accuracy:
Voltage .............................. :
Frequency ......................... :
Phase angle ...................... :
Temperature resistance
Voltage .............................. :
Frequency ......................... :
Phase angle ...................... :
Supply voltage:
Absolute Limits .......................... :
Power consumption .................... :
General information:
"Power On" startup delay............ :
Blocking Input B response time
Vector surge trip delay............... :
Ambient temperature range
LCD display contrast ................... :
Contact data (ohm resistive load, see Fig. 2)
Max. switching power ................. :
Max. switch voltage ..................... :
Max. switch current ..................... :
Electrical lifetime ........................ :
Insulation:
Line input - Supply input ............:
Line input - Relay outputs ......... :
Safety: ........................... : EN 61010
EMC:
Interference emission
Interference resistance : EN 61000-6-4 (Industry)
Front installation: Control panel cut-out 92x68mm (WxH)
CDMR62e_man_A1.doc
/ Operating instructions
(other values on request)
:
3x 100-110V / 57-64VAC
up to 145V / 82V
2 Un
500 k
45 - 65 Hz
<= 0.2% Un
0,01 Hz
+/- 0,5°
< 0.01% / °C
no dependency
+/- 0.006° / °C
70 – 300V AC / 45 – 65 Hz, 19.2 V - 250 V DC (limit values)
3 VA max.
0.3 s
(after U
:
40ms
60 – 80 ms
-20 C to +60 C
:
-5 C to +50 C
2000 VA / 240 W
250 V AC / 230 V DC
8 A (250 V AC / 30 V DC)
0.4 A (230 V DC)
5
10
switching cycles
2.5 kV
4.0 kV
: EN 61000-6-2 (Industry)
(100% ED)
(per phase)
(AC/DC Wide range power supply)
failure)
H
Mechanical data:
Housing DIN43700 .......... : 96 x 72 x 90 mm
Mounting .......................... : Front panel or DIN Rail 35mm
Material ............................ : Noryl
Flammability .................... : UL94-V0
Protection class ............... : Front IP50 / rear IP30
Terminals ......................... : 2.5 mm², pluggable
Installation width with rail adapter: 115mm
Page 2