- ページ 9

リモコン Daikin MadokaのPDF 設置および操作マニュアルをオンラインで閲覧またはダウンロードできます。Daikin Madoka 12 ページ。 Wired
Daikin Madoka にも: ユーザーマニュアル (2 ページ), 設置および操作マニュアル (13 ページ)

Daikin Madoka 設置および操作マニュアル
a
b
a
Installation and operation manual
b
Wood screws + wall plugs (Ø4.0×30)
8

Preparation

8.1

Wiring requirements

All wiring must comply with the following requirements:
Wire specification
Type
Section
Maximum length
9

Installation

9.1

Mounting the controller

Before you can mount the controller, you have to determine the
wiring routing, and accordingly, remove a piece of the controller's
rear casing.
The wiring can be routed from the top, the rear, the left, or the
bottom. Remove a piece of the rear casing according to the
illustration:
a
c
a
Wiring from the top
b
Wiring from the left
c
Wiring from the bottom
In case you are routing the wiring from the rear, you don't have to
remove anything.
9.1.1

To mount the controller

1 Take the screws and plugs from the accessory bag.
2 Mount the rear casing to a flat surface.
BRC1H82W+S
Madoka wired remote controller
4P596265-1 – 2019.11
Value
Sheathed vinyl cord or cable (2
wires)
2
0.75~1.25 mm
500 m
b
INFORMATION
If required (e.g. when mounting to a flush-mounted
electrical installation box), mount the rear casing by way of
the knockout holes.
NOTICE
When mounting the rear casing to a flush-mounted
electrical installation box inside a wall, make sure that that
wall is completely flat.
NOTICE
Be careful not to distort the rear casing by overtightening
the mounting screws.
9.2

Connecting the electrical wiring

NOTICE
The wiring for connection is NOT included.
NOTICE
When wiring, run the wiring away from the power supply
wiring in order to avoid receiving electric noise (external
noise).
9.2.1

To connect the electrical wiring

Connect controller terminals P1/P2 to indoor unit terminals P1/P2.
From the top
8 Preparation
P1P2
Installation and operation manual
9